Overview
- UPC Code
- 037332236258
- UPS Type
- On-Line
Output
- Output Volt Amp Capacity (VA)
- 8000
- Output kVA Capacity (kVA)
- 8
- Output Watt Capacity (Watts)
- 7200
- Output kW Capacity (kW)
- 7.2
- Power Factor
- 0.9
- Crest Factor
- 3:1
- Nominal Voltage Details
- 7200 watts total output supported; 5000 watts maximum 120V output; Add 1 additional SU5000XFMR2UTAA transformer for full load 120V operation; Voltage selection via front panel LCD interface; This configuration requires the Power Module be set to 208V output voltage; Included step-down transformer supports 120V output
- Frequency Compatibility
- 60 Hz
- Frequency Compatibility Details
- Output frequency regulation +/- 0.05Hz (free running)
- Output Voltage Regulation (Line Mode)
- +/- 2%
- Output Voltage Regulation (Economy Line Mode)
- +/- 10%
- Output Voltage Regulation (Battery Mode)
- +/- 2%
- Output Circuit Breakers
- 20A double-pole (x2) protects 2 L6-20R outlets each, 30A double-pole (x2) protects 1 L6-30R outlets each, 20A single-pole (x4) protect 3 5-15/20R outlets each
- Output AC Waveform (AC Mode)
- Pure Sine wave
- Output AC Waveform (Battery Mode)
- Pure Sine wave
- Output Capacity Details
- Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as load levels are reduced to 95% or less
- Nominal Output Voltage(s) Supported
- 120V; 208V
- Output Receptacles
- (12) 5-15/20R; (4) L6-20R; (2) L6-30R
- Individually Controllable Load Banks
- No
Input
- Rated input current (Maximum Load)
- 44.2A (208V)
- Nominal Input Voltage(s) Supported
- 208V AC
- UPS Input Connection Type
- Hardwire
- UPS Input Connection Description
- 3 wire single phase input (L1, L2, G)
- Recommended Electrical Service
- 50A
- Input Phase
- Single-Phase
Battery
- Full Load Runtime (min.)
- 5.5 min. (7200w)
- Half Load Runtime (min.)
- 13.5 min. (3600w)
- Expandable Battery Runtime
- Supports extended runtime with optional external battery packs
- External Battery Pack Compatibility
- BP240V10RT3UTAA ; BP240V787C-1PH
- DC System Voltage (VDC)
- 240
- Battery Recharge Rate (Included Batteries)
- Less than 6 hours from 10% to 90% (typical, full load discharge)
- Battery Replacement Description
- Hot-swappable, user replaceable external battery packs
- Expandable Runtime
- Yes
Voltage Regulation
- Voltage Regulation Description
- 2% output voltage regulation in standard online, double-conversion mode
- Overvoltage Correction
- Corrects overvoltages up to 300V
- Undervoltage Correction
- Corrects undervoltages as low as 100V
User Interface, Alerts & Controls
- Front Panel LCD Display
- Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats; LCD Display supports ENGLISH, FRENCH, GERMAN, ITALIAN, SPANISH and PORTUGUESE (see manual)
- Switches
- 2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module replacement
- Alarm Cancel Operation
- Alarm cancel switch
- Audible Alarm
- Unique audible alarms for all major UPS, environmental and power conditions (see manual)
- LED Indicators
- 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options
Surge / Noise Suppression
- UPS AC Suppression Joule Rating
- 2565
- UPS AC Suppression Response Time
- Instantaneous
- EMI / RFI AC Noise Suppression
- Yes
Isolation
- Output Isolation Transformer
- 120V output is isolation transformer protected
Physical
- Cooling Method
- Fan
- Included Battery Pack Dimensions (hwd / in.)
- 5.25 x 17.5 x 25
- Included Battery Pack Weight (lbs.)
- 159
- Included Mounting Accessory Description
- 3 sets of adjustable 4 post rack rails included; 2-9USTAND tower kit included
- Installation Form Factors Supported with Included Accessories
- 4 post 19 inch rackmount
- Installation Form Factors Supported with Optional Accessories
- 2 post rackmount ( 2POSTRMKITHD )
- Maximum Device Depth (in.)
- 33
- Minimum Required Rack Depth (inches)
- 38
- Optional Mounting Accessory Notes
- 3 sets of 2POSTRMKITHD required for 2 post rackmount installation of separate power module, battery pack and transformer
- Primary Form Factor
- Rackmount
- Primary UPS Depth (mm)
- 656
- Primary UPS Height (mm)
- 131
- Primary UPS Width (mm)
- 445
- Rack Height
- 8U
- Shipping Dimensions (hwd / in.)
- 31.50 x 26.00 x 41.00
- Shipping Weight (lbs.)
- 402.16
- Stepdown Transformer Depth (mm)
- 528
- Stepdown Transformer Dimensions (hwd / in.)
- 3.5 x 17.5 x 20.8
- Stepdown Transformer Height (mm)
- 89
- Stepdown Transformer Weight (lbs.)
- 57
- Stepdown Transformer Width (mm)
- 445
- UPS Dimensions Details
- Includes 3U UPS/power module, 3U battery pack, 2U SU5000XFMR2UTAA step down transformer plus SUPDMB710TAA PDU with bypass; MAXIMUM DEVICE DEPTH specification refers to the whole UPS installed depth with bypass PDU installed
- UPS Housing Material
- Steel
- UPS Power Module Dimensions (hwd, in.)
- 5.14 x 17.5 x 25.82
- UPS Power Module Weight (kg)
- 19.50
- UPS Power Module Weight (lbs.)
- 43
Environmental
- Operating Temperature Range
- +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- Storage Temperature Range
- +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
- Relative Humidity
- 0 to 95%, non-condensing
- AC Mode BTU / Hr. (Full Load)
- 2732
- AC Economy Mode BTU / Hr. (Full Load)
- 1024
- Battery Mode BTU / Hr. (Full Load)
- 2432
- AC Mode Efficiency Rating (100% Load)
- 91%
- AC Economy Mode Efficiency Rating (100% Load)
- 96%
- Operating Elevation (ft.)
- 0 to 10,000 ft.
- Audible Noise
- 60 dBA at front side 1 meter
- Operating Elevation (m)
- 0-3000 m
Communications
- Network Management Cards
- SNMPWEBCARD ; TLNETCARD ; WEBCARDLX ; MODBUSCARD ; RELAYIOCARD
- Network Monitoring Port Description
- Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports
- PowerAlert Software
- For local monitoring via the UPS’s built-in communication ports , download PowerAlert Local software at http://www.tripplite.com/poweralert
- Communications Cable
- USB, DB9 serial and EPO cables included
- WatchDog Compatibility
- Supports Watchdog application, OS and hard-reboot restart options for remote applications
- Communications Interface
- USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Line / Battery Transfer
- Transfer Time
- No transfer time (0 ms.) in online, double-conversion mode
- Transfer Time (Economy Mode)
- 8 ms. typical power failure response in optional economy mode
- Low Voltage Transfer to Battery Power (Setpoint)
- 100V
- High Voltage Transfer to Battery Power (Setpoint)
- 300V
Special Features
- Cold Start (Startup in Battery Mode During a Power Failure)
- Cold-start operation supported
- Economy Mode Operation
- Optional economy mode enables high-efficiency bypass operation with a maximum output voltage variation of +/-10%. Double conversion mode is automatically restored as mains voltage varies beyond +/-10% with less than 1 millisecond transfer time between modes.
- High Availability UPS Features
- Automatic inverter bypass; Battery Independent Restart; Hot swappable UPS power module; Hot swappable batteries; Manual bypass switch
- Green Energy-Saving Features
- High efficiency economy mode operation; Schedulable daily hours of economy mode operation
Certifications
- UPS Certifications
- Meets FCC Part 15 Category A (EMI); TAA Compliant; Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA)
- UPS Certification Details
- IEC 61000-4-5 1995 B Surge Immunity
Warranty
- Product Warranty Period (Worldwide)
- 2-year limited warranty
- Connected Equipment Insurance (U.S., Canada & Puerto Rico)
- $250,000 Ultimate Lifetime Insurance
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther