A total of 211 Parts In-Stock from 9 Distributors

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Nominal voltage (III/3)
500 V
Rated impulse voltage (III/3)
6 kV
Rated current
24 A
Current at conductor cross-section (max.) mm²
28 A
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
5.2 mm / 0.205 inches
Height
69.7 mm / 2.744 inches
Depth from upper-edge of DIN-rail
61.8 mm / 2.433 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Gray
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.218 MJ
Weight
10.603 g

Mechanical Data

Potential marking
L/N
Mounting type
DIN-35 rail
Marking level
Center/side marking

Connection 2

Number of connection points 2
2

Specifications

Product Group Code
0022

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4044918989831
Customs tariff number
85369010000

Ex Information

Reference hazardous areas
See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Ratings per
ATEX: PTB 03 ATEX 1162 U / IECEx: PTB 03.0004U (Ex eb IIC Gb)
Rated voltage EN (Ex e II)
440 V
Rated current (Ex e II)
20 A
Rated current (Ex e II) with jumper
18 A

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
600 V
Rated current CSA (Use Group B)
20 A
Rated voltage CSA (Use Group C)
600 V
Rated current CSA (Use Group C)
20 A

Power Loss

Power loss, per pole (potential)
0.7661 W
Rated current IN for specified power loss
24 A
Resistance value for specified, current-dependent power loss
0.00133 Ω

Connection 1

Connection technology
Push-in CAGE CLAMP®
Number of connection points
2
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm²
Solid conductor
0.25 … 4 mm² / 22 … 12 AWG
Solid conductor; push-in termination
0.75 … 4 mm² / 18 … 12 AWG
Fine-stranded conductor
0.25 … 4 mm² / 22 … 12 AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5 mm² / 22 … 14 AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5 mm² / 18 … 14 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12 mm / 0.39 … 0.47 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
300 V
Rated current UL (Use Group B)
20 A
Rated voltage UL (Use Group C)
300 V
Rated current UL (Use Group C)
20 A
Rated voltage UL (Use Group D)
600 V
Rated current UL (Use Group D)
5 A

Related products