Wago

2002-3248

Triple-deck terminal block; shield/through/through (Shield/N/L); with marker carrier; rail mount; 2-conductor; 5.2 mm wide; gray
2002-3248
2002-3248
2002-3248
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€24.72
1
Payment methods:
A total of 200 Parts In-Stock from 9 Distributors

Additional Information

Part Number
2002-3248
UPC
4044918989657
Tariff Code
85369010000
ETIM
Group Code : EG000012
Group Description : Terminal blocks
Class Description : Ground terminal block
Class Code : EC000901
Version : 7

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Nominal voltage (III/3)
500 V
Rated impulse voltage (III/3)
6 kV
Rated current
24 A
Current at conductor cross-section (max.) mm²
28 A
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
5.2 mm / 0.205 inches
Height
93.3 mm / 3.673 inches
Depth from upper-edge of DIN-rail
81.3 mm / 3.201 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Gray
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.326 MJ
Weight
20.356 g

Mechanical Data

Potential marking
Shield/N/L
Mounting type
DIN-35 rail
Marking level
Center/side marking

Connection 2

Number of connection points 2
3

Specifications

Product Group Code
0022

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4044918989657
Customs tariff number
85369010000

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
600 V
Rated current CSA (Use Group B)
20 A
Rated voltage CSA (Use Group C)
600 V
Rated current CSA (Use Group C)
20 A

Power Loss

Power loss, per pole (potential)
2.2982 W
Rated current IN for specified power loss
24 A
Resistance value for specified, current-dependent power loss
0.00133 Ω

Connection 1

Connection technology
Push-in CAGE CLAMP®
Number of connection points
3
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm²
Solid conductor
0.25 … 4 mm² / 22 … 12 AWG
Solid conductor; push-in termination
0.75 … 4 mm² / 18 … 12 AWG
Fine-stranded conductor
0.25 … 4 mm² / 22 … 12 AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5 mm² / 22 … 14 AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5 mm² / 18 … 14 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12 mm / 0.39 … 0.47 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
300 V
Rated current UL (Use Group B)
20 A
Rated voltage UL (Use Group C)
300 V
Rated current UL (Use Group C)
20 A
Rated voltage UL (Use Group D)
600 V
Rated current UL (Use Group D)
5 A

Related products