A total of 400 Parts In-Stock from 7 Distributors

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Ratings (note)
Potential – ground
Nominal voltage (III/3)
250 V
Rated impulse voltage (III/3)
4 kV
Rated current
24 A
Current at conductor cross-section (max.) mm²
28 A
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Ratings Per Iec/En 2

Ratings per 2
IEC/EN 60947-7-1
Ratings (note) 2
Potential – potential
Rated voltage (III/3) 2
400 V
Rated surge voltage (III/3) 2
6 kV
Rated current 2
24 A
Current at conductor cross-section (max.) 2
25 A

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
5.2 mm / 0.205 inches
Height
110 mm / 4.331 inches
Depth from upper-edge of DIN-rail
45.2 mm / 1.78 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Gray
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.308 MJ
Weight
20.052 g

Mechanical Data

Potential marking
L/L/PE
Mounting type
DIN-35 rail
Marking level
Center/side marking

Specifications

Product Group Code
0022

Commercial Data

Packaging type
Box
Country of origin
CN
GTIN
4050821322054
Customs tariff number
85369010000

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
300 V
Rated current CSA (Use Group B)
20 A
Rated voltage CSA (Use Group D)
150 V || 300 V
Rated current CSA (Use Group D)
15 A || 10 A

Power Loss

Power loss, per pole (potential)
0.7661 W
Rated current IN for specified power loss
24 A
Resistance value for specified, current-dependent power loss
0.00133 Ω

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm²
Solid conductor
0.25 … 4 mm² / 22 … 12 AWG
Solid conductor; push-in termination
0.75 … 4 mm² / 18 … 12 AWG
Fine-stranded conductor
0.25 … 4 mm² / 22 … 12 AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5 mm² / 22 … 14 AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5 mm² / 18 … 14 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12 mm / 0.39 … 0.47 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
300 V
Rated current UL (Use Group B)
20 A
Rated voltage UL (Use Group C)
300 V
Rated current UL (Use Group C)
20 A
Rated voltage UL (Use Group D)
300 V
Rated current UL (Use Group D)
20 A

Related products