Wago

2004-1402

TOPJOB®S feedthrough terminal block; rail mount; 3-conductor; 6.2 mm wide; orange
2004-1402
2004-1402
2004-1402
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€1.26
1
Payment methods:
A total of 612 Parts In-Stock from 14 Distributors

Additional Information

Part Number
2004-1402
UPC
4017332071802
Tariff Code
85369010000
ETIM
Group Code : EG000012
Group Description : Terminal blocks
Class Description : Feed-through terminal block
Class Code : EC000897
Version : 7

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Nominal voltage (III/3)
800 V
Rated impulse voltage (III/3)
8 kV
Rated current
32 A
Current at conductor cross-section (max.) mm²
41 A
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
6.2 mm / 0.244 inches
Height
78.7 mm / 3.098 inches
Depth from upper-edge of DIN-rail
32.9 mm / 1.295 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Orange
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.181 MJ
Weight
10.476 g

Mechanical Data

Mounting type
DIN-35 rail
Marking level
Center/side marking

Specifications

Product Group Code
0022

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4017332071802
Customs tariff number
85369010000

Ex Information

Reference hazardous areas
See application instructions in section “Knowledge and Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Ratings per
ATEX: PTB 05 ATEX 1095 U / IECEx: PTB 05.0033U (Ex eb IIC Gb)
Rated voltage EN (Ex e II)
550 V
Rated current (Ex e II)
30 A

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
600 V
Rated current CSA (Use Group B)
30 A
Rated voltage CSA (Use Group C)
600 V
Rated current CSA (Use Group C)
30 A

Power Loss

Power loss, per pole (potential)
1.024 W
Rated current IN for specified power loss
32 A
Resistance value for specified, current-dependent power loss
0.001 Ω

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
4 mm²
Solid conductor
0.5 … 6 mm² / 20 … 10 AWG
Solid conductor; push-in termination
1.5 … 6 mm² / 14 … 10 AWG
Fine-stranded conductor
0.5 … 6 mm² / 20 … 10 AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 4 mm² / 20 … 12 AWG
Fine-stranded conductor; with ferrule; push-in termination
1.5 … 4 mm² / 18 … 12 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
11 … 13 mm / 0.43 … 0.51 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
600 V
Rated current UL (Use Group B)
30 A
Rated voltage UL (Use Group C)
600 V
Rated current UL (Use Group C)
30 A