Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Nominal voltage (III/3)
800 V
Rated impulse voltage (III/3)
8 kV
Rated current
76 A
Current at conductor cross-section (max.) mm²
90 A
Note (rated current)
15 mm high DIN-35 rails shall be used for a current load higher than 76 A!
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
12 mm / 0.472 inches
Height
69.8 mm / 2.748 inches
Depth from upper-edge of DIN-rail
36.9 mm / 1.453 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Black
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.438 MJ
Weight
22.630 g

Mechanical Data

Mounting type
DIN-35 rail
Marking level
Center/side marking

Specifications

Product Group Code
0022

Commercial Data

Country of origin
DE
GTIN
4066966311594
Customs tariff number
85369010000

Ex Information

Reference hazardous areas
See application instructions in section “Knowledge and Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Ratings per
ATEX: PTB 05 ATEX 1031 U / IECEx: PTB 05.0015U (Ex eb IIC Gb)
Rated voltage EN (Ex e II)
550 V
Rated current (Ex e II)
70 A
Rated current (Ex e II) with jumper
67 A

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
600 V
Rated current CSA (Use Group B)
80 A
Rated voltage CSA (Use Group C)
600 V
Rated current CSA (Use Group C)
80 A

Power Loss

Power loss, per pole (potential)
2.4259 W
Rated current IN for specified power loss
76 A
Resistance value for specified, current-dependent power loss
0.00042 Ω

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
16 mm²
Solid conductor
0.5 … 16 mm² / 20 … 6 AWG
Solid conductor; push-in termination
6 … 16 mm² / 14 … 6 AWG
Fine-stranded conductor
0.5 … 25 mm² / 20 … 4 AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 16 mm² / 20 … 6 AWG
Fine-stranded conductor; with ferrule; push-in termination
6 … 16 mm² / 10 … 6 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
18 … 20 mm / 0.71 … 0.79 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
600 V
Rated current UL (Use Group B)
85 A
Rated voltage UL (Use Group C)
600 V
Rated current UL (Use Group C)
85 A