Wago

2106-1304

TOPJOB®S feedthrough terminal block with Lever and Open Tool Slost; rail mount; 3-conductor; 7.5 mm wide; blue
2106-1304
2106-1304
2106-1304
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 24 Parts In-Stock from 8 Distributors

Additional Information

Part Number
2106-1304
UPC
4055143742061
Tariff Code
85369010000
ETIM
Group Code : EG000012
Group Description : Terminal blocks
Class Description : Feed-through terminal block
Class Code : EC000897
Version : 7

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Nominal voltage (III/3)
800 V
Rated impulse voltage (III/3)
8 kV
Rated current
41 A
Current at conductor cross-section (max.) mm²
55 A
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
7.5 mm / 0.295 inches
Height
90.8 mm / 3.575 inches
Depth from upper-edge of DIN-rail
32.9 mm / 1.295 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Blue
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.393 MJ
Weight
17.650 g

Mechanical Data

Mounting type
DIN-35 rail
Marking level
Center/side marking

Connection 2

Actuation type 2
Operating tool

Specifications

Product Group Code
0035

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4055143742061
Customs tariff number
85369010000

Ex Information

Reference hazardous areas
See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Ratings per
ATEX: PTB 18 ATEX 1011 U / IECEx: PTB 18.0018U (Ex eb IIC Gb)
Rated voltage EN (Ex e II)
550 V
Rated current (Ex e II)
41 A
Rated current (Ex e II) with jumper
33 A

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
600 V
Rated current CSA (Use Group B)
45 A
Rated voltage CSA (Use Group C)
600 V
Rated current CSA (Use Group C)
45 A

Power Loss

Power loss, per pole (potential)
1.3112 W
Rated current IN for specified power loss
41 A
Resistance value for specified, current-dependent power loss
0.00078 Ω

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Lever
Connectable conductor materials
Copper
Nominal cross-section
6 mm²
Solid conductor
0.5 … 10 mm² / 20 … 8 AWG
Solid conductor; push-in termination
1 … 10 mm² / 14 … 8 AWG
Fine-stranded conductor
0.5 … 10 mm² / 20 … 8 AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 6 mm² / 20 … 10 AWG
Fine-stranded conductor; with ferrule; push-in termination
2.5 … 6 mm² / 16 … 10 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
13 … 15 mm / 0.51 … 0.59 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
600 V || 600 V
Rated current UL (Use Group B)
50 A || 30 A
Rated voltage UL (Use Group C)
600 V || 600 V
Rated current UL (Use Group C)
50 A || 30 A
Rated voltage UL (Use Group D)
600 V
Rated current UL (Use Group D)
5 A

Related products