Wago

2202-1911/1000-541

TOPJOB®S fuse terminal block with Push-buttons; with pivoting fuse holder for 5 x 20 mm miniature metric fuse; with LED blown fuse indication; rail mount; 2-conductor; 5.2 mm wide; gray, 12 - 30 V
2202-1911/1000-541
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€4.39

Additional Information

Part Number
2202-1911/1000-541
UPC
4066966333961
Tariff Code
85369095000
ETIM
Group Code : EG000012
Group Description : Terminal blocks
Class Description : Fuse terminal block
Class Code : EC000899
Version : 7

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-3
Ratings (note)
Electrical ratings are given by the fuse and blown fuse indication.
Nominal voltage (III/3)
250 V
Rated impulse voltage (III/3)
6 kV
Rated current
6.3 A
Note (rated current)
Leakage current in case of a blown fuse: LED 2.2 mA (at 24 V operating voltage)
Operation status indicator
12 … 30 V
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Ratings Per Iec/En 2

Ratings per 2
IEC/EN 60947-7-3
Rated voltage (III/3) 2
30 V
Rated surge voltage (III/3) 2
0.8 kV

Environmental Requirements

Ambient temperature (operation)
-35 … +70 °C
Processing temperature
-35 … +70 °C
Continuous operating temperature
-35 … +70 °C

Physical Data

Width
6.2 mm / 0.244 inches
Height
72.9 mm / 2.87 inches
Depth from upper-edge of DIN-rail
57.6 mm / 2.268 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Gray
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.259 MJ
Weight
14.460 g

Mechanical Data

Mounting type
DIN-35 rail
Marking level
Center/side marking

General

Fuse receptacle
Pivoting
Fuse type
Cylindrical fuse; 5 x 20 mm

Specifications

Product Group Code
0036

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4066966333961
Customs tariff number
85369095000

Ex Information

Reference hazardous areas
See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Ratings per
ATEX: PTB 20 ATEX 1007 U / IECEx: PTB 20.0013U (Ex ec IIC Gc)
Rated voltage EN (Ex e II)
275 V
Rated current (Ex e II)
6.3 A

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
30 V
Rated current CSA (Use Group B)
10 A
Rated voltage CSA (Use Group C)
30 V
Rated current CSA (Use Group C)
10 A
Rated voltage CSA (Use Group D)
30 V
Rated current CSA (Use Group D)
10 A

Power Loss

Power loss Pl max. overload and short-circuit protection (individual arrangement)
1.6 W
Power loss Pl max. overload and short-circuit protection (group arrangement)
1.6 W
Power loss Pl max. short-circuit protection (individual arrangement)
2.5 W
Power loss Pl max. short-circuit protection (group arrangement)
2.5 W

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Push-button
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm²
Solid conductor
0.25 … 4 mm² / 22 … 12 AWG
Solid conductor; push-in termination
0.75 … 4 mm² / 18 … 12 AWG
Fine-stranded conductor
0.25 … 4 mm² / 22 … 12 AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5 mm² / 22 … 14 AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5 mm² / 18 … 14 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12 mm / 0.39 … 0.47 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
30 V
Rated current UL (Use Group B)
10 A
Rated voltage UL (Use Group C)
30 V
Rated current UL (Use Group C)
10 A
Rated voltage UL (Use Group D)
30 V