Wago

285-187

POWER CAGE CLAMP feedthrough terminal block; with fixing flanges; 2-conductor; 4/0 AWG; 25 mm wide; dark gray-yellow
285-187
285-187
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:

Additional Information

Part Number
285-187
UPC
4055143583954
Tariff Code
85369010000
ETIM
Group Code : EG000012
Group Description : Terminal blocks
Class Description : Feed-through terminal block
Class Code : EC000897
Version : 7

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-2
Nominal voltage (III/3)
1000 V
Rated impulse voltage (III/3)
12 kV
Rated current
232 A

Ratings Per Iec/En 2

Rated voltage (III/3) 2
1500 V
Rated surge voltage (III/3) 2
12 kV

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
25 mm / 0.984 inches
Height from the surface
108 mm / 4.252 inches
Depth
145 mm / 5.709 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Dark gray-yellow
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.956 MJ
Weight
268.171 g

Mechanical Data

Mounting type
Mounting flange
Marking level
Side marking

General

Voltage type 1
AC/DC
Voltage type 2
DC

Specifications

Product Group Code
0001

Commercial Data

Packaging type
Box
Country of origin
PL
GTIN
4055143583954
Customs tariff number
85369010000

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
1000 V
Rated current CSA (Use Group B)
210 A
Rated voltage CSA (Use Group C)
1000 V
Rated current CSA (Use Group D)
210 A

Power Loss

Power loss, per pole (potential)
7.5354 W
Rated current IN for specified power loss
232 A
Resistance value for specified, current-dependent power loss
0.00014 Ω

Connection 1

Connection technology
POWER CAGE CLAMP
Actuation type
T-wrench; 8 mm
Connectable conductor materials
Copper
Solid conductor
25 … 95 mm² / 4 … 4/0 AWG
Stranded conductor
25 … 95 mm² / 4 … 4/0 AWG
Fine-stranded conductor
25 … 95 mm² / 4 … 4/0 AWG
Fine-stranded conductor; with insulated ferrule
25 … 95 mm² / 4 … 4/0 AWG
Fine-stranded conductor; with uninsulated ferrule
25 … 95 mm² / 4 … 4/0 AWG
Strip length
35 mm / 1.38 inches
Wiring direction
Side-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
600 V
Rated current UL (Use Group B)
200 A
Rated voltage UL (Use Group C)
600 V
Rated current UL (Use Group C)
200 A

Related products