Wago
2857-533
JUMPFLEX® signal conditioner; RTD threshold value switch; with picoMAX® connector; configurable
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
€157.33
1
Payment methods:
A total of 6 Parts In-Stock from 12 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€129.26
Additional Information
- Part Number
- 2857-533
- UPC
- 4050821676973
- Tariff Code
- 90303370000
- ETIM
- Group Code : EG000019
- Group Description : Relays
- Class Description : Temperature monitoring relay
- Class Code : EC001446
- Version : 7
Signal Processing
- Software filter (adjustable)
- Moving average value (filter level: 30)
- Hysteresis
- Adjustable via DIP switch or software
- Step response (typ.)
- 60 ms (2-wire); 360 ms (3-wire); 540 ms (4-wire); 360 ms (Potentiometer)
Configuration
- Configuration options
- DIP switch || WAGO Interface Configuration Software || WAGO Interface Configuration App || WAGO Configuration Display
Environmental Requirements
- Ambient temperature (operation)
- -40 … +70 °C
- Ambient temperature (storage)
- -40 … +85 °C
- Temperature range of connection cable
- ≥ (Tambient + 10 K)
- Temperature range of connection cable (UL)
- 80 °C
Output (Digital)
- Switching voltage (DO) max.
- Supply voltage (applied): −0.3 V
- Continuous current (DO) max.
- 100 mA (no internal restriction)
- Number of switching thresholds (DO)
- 1 or 2 (adjustable)
- Configurable rise/fall delay time (DO)
- 0 … 60 s (via software)
Connection Data
- Connection technology
- Push-in CAGE CLAMP®
- WAGO connector
- picoMAX® 5.0
- Solid conductor
- 0.2 … 2.5 mm² / 24 … 12 AWG
- Fine-stranded conductor
- 0.2 … 2.5 mm² / 24 … 12 AWG
- Strip length
- 9 … 10 mm / 0.35 … 0.39 inches
Signaling And Communication
- Configuration options
- DIP switch || WAGO Interface Configuration Software || WAGO Interface Configuration App || WAGO Configuration Display
Output (Relay)
- Number of make/switch-on contacts
- 1
- Contact material (relay)
- AgNi + Au
- Switching voltage (max.)
- AC 250 V
- Dielectric strength (open contact) (AC, 1 min)
- 1 kVrms
- Pull-in time (typ.)
- 8 ms
- Drop-out time (typ.)
- 4 ms
- Bounce time (typ.)
- 8 ms
- Number of switching thresholds (relay)
- 1 or 2 (adjustable)
- Configurable rise/fall delay time (relay)
- 0 … 60 s (via software)
Input (Rtd Sensors)
- Sensor types (RTD)
- Pt100 || Pt200 || Pt500 || Pt1000 || Pt5000 || Pt10000 || Pt10 … Pt20000
- Sensor connection
- 2-wire; 3-wire; 4-wire; differential
- Sensor power supply (RTD) max.
- ≤ 0.5 mA
- Temperature measurement range (RTD)
- -200 … 850°C
Supply
- Power supply type
- 24 VDC
- Nominal supply voltage US
- DC 24 V
- Supply voltage range
- ±30 %
- Current consumption at nominal supply voltage
- ≤ 40 mA (+ IDO)
Physical Data
- Width
- 12.5 mm / 0.492 inches
- Height
- 110 mm / 4.331 inches
- Depth from upper-edge of DIN-rail
- 107 mm / 4.213 inches
Measurement Error
- Transmission error (max.)
- ± 1 K
- Temperature coefficient
- ≤ 0.01 %/K
Material Data
- Fire load
- 1.573 MJ
- Weight
- 86.500 g
Input
- Input signal type
- RTD sensors || Potentiometer || Resistance
Insulation Parameters(Ul)
- Overvoltage category
- II
- Pollution degree
- 2
- Insulation type (input, supply and service interface/relay output)
- Reinforced insulation (safe isolation)
- Insulation type (input/supply/service interface)
- Basic insulation
Standards And Specifications
- Conformity marking
- CE
- EMC immunity to interference
- EN 61000-6-2; EN 61326-2-3; EN 50121-3-2
- EMC emission of interference
- EN 61000-6-4; EN 61326-2-3; EN 50121-3-2
- Standards/specifications
- EN 61010-1 || EN 61373 || EN 50121-3-2
Mechanical Data
- Mounting type
- DIN-35 rail
Specifications
- Product Group Code
- 0006
Commercial Data
- Packaging type
- Bag
- Country of origin
- DE
- GTIN
- 4050821676973
- Customs tariff number
- 90303370000
Notes
- Note
- This product is supplied with 24 VDC, which can be commoned using lateral push-in type jumper bars: (6.1) US+ (BR) and (6.2) GND 2 (BR). With this variant, it is necessary to ensure that the maximum permissible total current of 2 A is not exceeded.Additional setting options via WAGO Interface Configuration Software or WAGO Interface Configuration App
Test Voltage
- Test voltage (input/relay output/supply)
- 4 kVAC; 60 Hz; 1 min
- Test voltage (input/service interface)
- 3 kVAC; 60 Hz; 1 min
- Test voltage (relay output/service interface)
- 4 kVAC; 60 Hz; 1 min
- Test voltage (supply/service interface)
- 2.5 kVAC; 60 Hz; 1 min
Input (Resistors)
- Input range (resistor)
- 0 … 100 kΩ
- Input range (potentiometer)
- 0 … 100 kΩ