Wago

2857-533

JUMPFLEX® signal conditioner; RTD threshold value switch; with picoMAX® connector; configurable
2857-533
2857-533
2857-533
2857-533
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€157.33
1
Payment methods:
A total of 6 Parts In-Stock from 12 Distributors
Offer with manufacturer lead time
Ships in:On Request
Best price:
€129.26

Additional Information

Part Number
2857-533
UPC
4050821676973
Tariff Code
90303370000
ETIM
Group Code : EG000019
Group Description : Relays
Class Description : Temperature monitoring relay
Class Code : EC001446
Version : 7

Signal Processing

Software filter (adjustable)
Moving average value (filter level: 30)
Hysteresis
Adjustable via DIP switch or software
Step response (typ.)
60 ms (2-wire); 360 ms (3-wire); 540 ms (4-wire); 360 ms (Potentiometer)

Configuration

Configuration options
DIP switch || WAGO Interface Configuration Software || WAGO Interface Configuration App || WAGO Configuration Display

Environmental Requirements

Ambient temperature (operation)
-40 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Temperature range of connection cable
≥ (Tambient + 10 K)
Temperature range of connection cable (UL)
80 °C

Output (Digital)

Switching voltage (DO) max.
Supply voltage (applied): −0.3 V
Continuous current (DO) max.
100 mA (no internal restriction)
Number of switching thresholds (DO)
1 or 2 (adjustable)
Configurable rise/fall delay time (DO)
0 … 60 s (via software)

Connection Data

Connection technology
Push-in CAGE CLAMP®
WAGO connector
picoMAX® 5.0
Solid conductor
0.2 … 2.5 mm² / 24 … 12 AWG
Fine-stranded conductor
0.2 … 2.5 mm² / 24 … 12 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches

Signaling And Communication

Configuration options
DIP switch || WAGO Interface Configuration Software || WAGO Interface Configuration App || WAGO Configuration Display

Output (Relay)

Number of make/switch-on contacts
1
Contact material (relay)
AgNi + Au
Switching voltage (max.)
AC 250 V
Dielectric strength (open contact) (AC, 1 min)
1 kVrms
Pull-in time (typ.)
8 ms
Drop-out time (typ.)
4 ms
Bounce time (typ.)
8 ms
Number of switching thresholds (relay)
1 or 2 (adjustable)
Configurable rise/fall delay time (relay)
0 … 60 s (via software)

Input (Rtd Sensors)

Sensor types (RTD)
Pt100 || Pt200 || Pt500 || Pt1000 || Pt5000 || Pt10000 || Pt10 … Pt20000
Sensor connection
2-wire; 3-wire; 4-wire; differential
Sensor power supply (RTD) max.
≤ 0.5 mA
Temperature measurement range (RTD)
-200 … 850°C

Supply

Power supply type
24 VDC
Nominal supply voltage US
DC 24 V
Supply voltage range
±30 %
Current consumption at nominal supply voltage
≤ 40 mA (+ IDO)

Physical Data

Width
12.5 mm / 0.492 inches
Height
110 mm / 4.331 inches
Depth from upper-edge of DIN-rail
107 mm / 4.213 inches

Measurement Error

Transmission error (max.)
± 1 K
Temperature coefficient
≤ 0.01 %/K

Material Data

Fire load
1.573 MJ
Weight
86.500 g

Input

Input signal type
RTD sensors || Potentiometer || Resistance

Insulation Parameters(Ul)

Overvoltage category
II
Pollution degree
2
Insulation type (input, supply and service interface/relay output)
Reinforced insulation (safe isolation)
Insulation type (input/supply/service interface)
Basic insulation

Standards And Specifications

Conformity marking
CE
EMC immunity to interference
EN 61000-6-2; EN 61326-2-3; EN 50121-3-2
EMC emission of interference
EN 61000-6-4; EN 61326-2-3; EN 50121-3-2
Standards/specifications
EN 61010-1 || EN 61373 || EN 50121-3-2

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Bag
Country of origin
DE
GTIN
4050821676973
Customs tariff number
90303370000

Notes

Note
This product is supplied with 24 VDC, which can be commoned using lateral push-in type jumper bars: (6.1) US+ (BR) and (6.2) GND 2 (BR). With this variant, it is necessary to ensure that the maximum permissible total current of 2 A is not exceeded.Additional setting options via WAGO Interface Configuration Software or WAGO Interface Configuration App

Test Voltage

Test voltage (input/relay output/supply)
4 kVAC; 60 Hz; 1 min
Test voltage (input/service interface)
3 kVAC; 60 Hz; 1 min
Test voltage (relay output/service interface)
4 kVAC; 60 Hz; 1 min
Test voltage (supply/service interface)
2.5 kVAC; 60 Hz; 1 min

Input (Resistors)

Input range (resistor)
0 … 100 kΩ
Input range (potentiometer)
0 … 100 kΩ

Related products