734-304/019-000

1-conductor male connector; CAGE CLAMP®; 1.5 mm²; Pin spacing 3.5 mm; 4-pole; 100% protected against mismating; clamping collar; 1,50 mm²; light gray
734-304/019-000
734-304/019-000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up

Ratings Per Iec/En

Ratings per
IEC/EN 60664-1
Nominal voltage (III/3)
160 V
Rated impulse voltage (III/3)
2.5 kV
Rated voltage (III/2)
160 V
Rated impulse voltage (III/2)
2.5 kV
Nominal voltage (II/2)
320 V
Rated surge voltage (II/2)
2.5 kV
Rated current
10 A
Legend (ratings)
(III / 2) ≙ Overvoltage category III / Pollution degree 2

Environmental Requirements

Limit temperature range
-60 … +100 °C
Processing temperature
-35 … +60 °C

Plug-In Connection

Contact type (pluggable connector)
Male connector/plug
Connector (connection type)
For conductor
Mismating protection
Yes
Plugging without loss of pin spacing
No
Locking of plug-in connection
None

Physical Data

Pin spacing
3.5 mm / 0.138 inches
Width
28.8 mm / 1.134 inches
Height
13.4 mm / 0.528 inches
Depth
22.3 mm / 0.878 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Light gray
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Clamping spring material
Chrome-nickel spring steel (CrNi)
Contact material
Electrolytic copper (ECu)
Contact plating
Tin
Fire load
0.090 MJ
Weight
4.288 g

Mechanical Data

Variable coding
Yes
Mounting type
Mounting flange || Feed-through mounting || Panel mounting
Anti-rotation protection
Yes

Specifications

Product Group Code
0003

Commercial Data

Packaging type
Box
Country of origin
PL
GTIN
4055143268844
Customs tariff number
85366990990

Notes

Safety information
The MCS – MULTI CONNECTION SYSTEM includes connectors without breaking capacity in accordance with DIN EN 61984. When used as intended, these connectors must not be connected/disconnected when live or under load.When used as intended, these connectors must not be connected/disconnected when live or under load. The circuit design should ensure header pins, which can be touched, are not live when unmated.
Variants:
Other pole numbers || Gold-plated or partially gold-plated contact surfaces || Other versions (or variants) can be requested from WAGO Sales or configured at https://configurator.wago.com/.

Ratings Per Csa

Approvals per
CSA
Rated voltage CSA (Use Group B)
300 V
Rated current CSA (Use Group B)
10 A
Rated voltage CSA (Use Group D)
300 V
Rated current CSA (Use Group D)
10 A

Connection 1

Connection technology
CAGE CLAMP®
Actuation type
Operating tool
Actuation direction 1
Operation parallel to conductor entry
Actuation direction 2
Operation perpendicular to conductor entry
Solid conductor
0.08 … 1.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.08 … 1.5 mm² / 28 … 14 AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 1.5 mm²
Fine-stranded conductor; with uninsulated ferrule
0.25 … 1.5 mm²
Note (conductor cross-section)
Terminating 1.5 mm² conductors is possible; however insulation diameter does not allow clamping units to be terminated in a row.
Strip length
6 … 7 mm / 0.24 … 0.28 inches
Pole number
4
Conductor entry direction to mating direction
0 °

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
300 V
Rated current UL (Use Group B)
10 A
Rated voltage UL (Use Group D)
300 V
Rated current UL (Use Group D)
10 A