Environmental Requirements

Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-25 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
Mounting position
Any
Relative humidity (without condensation)
95 %
Vibration resistance
4g per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
Per EN 61000-6-2, marine applications
EMC emission of interference
Per EN 61000-6-4, marine applications
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %
10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %
25 ppm

Connection Data

Connection technology: inputs/outputs
8 x CAGE CLAMP®
Connection type 1
Inputs/outputs
Solid conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Strip length
8 … 9 mm / 0.31 … 0.35 inches

Physical Data

Width
12 mm / 0.472 inches
Height
69.8 mm / 2.748 inches
Height from upper-edge of DIN-rail
62.6 mm / 2.465 inches
Depth
100 mm / 3.937 inches

Material Data

Color
Light gray
Housing material
Polycarbonate; polyamide 6.6
Fire load
1.014 MJ
Weight
51.500 g
Conformity marking
CE

Technical Data

Number of analog inputs
2
Total number of channels (module)
2
Signal type
Resistance measurement
Sensor connection
2 x (2-wire, 3-wire)
Data width
2 x 16-bit data; 2 x 8-bit control/status (optional)
Resolution (over entire range)
0.1 °C
Conversion time (typ.)
320 ms
Measurement error (reference temperature)
25 °C
Measurement error, deviation (max.) from the upper-range value
0.2 %
Temperature error (max.) of the upper-range value
0.01 %/K
Measuring current (typ.)
0.5 mA
Response time (max.)
4 s
Sensor types
Ni100
Temperature range
−60 … +250 °C
Supply voltage (system)
5 VDC; via data contacts
Current consumption (5 V system supply)
80 mA
Isolation
500 V system/field

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0015

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4045454486860
Customs tariff number
85389099990

Related products