Wago

750-471/040-000

4-channel analog input; Voltage/Current; Differential input; 16 bits; Diagnostics; Extreme
750-471/040-000
750-471/040-000
750-471/040-000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€444.00
1
Payment methods:
A total of 50 Parts In-Stock from 6 Distributors

Environmental Requirements

Ambient temperature (operation)
-40 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
Mounting position
Horizontal (standing/lying); vertical
Relative humidity (without condensation)
95 %
Relative humidity (with condensation)
Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Vibration resistance
Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
Shock resistance
Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
EMC immunity to interference
Per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
EMC emission of interference
Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %
10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %
25 ppm

Connection Data

Connection technology: inputs/outputs
8 x CAGE CLAMP®
Connection type 1
Inputs/outputs
Solid conductor
0.25 … 2.5 mm² / 24 … 14 AWG
Fine-stranded conductor
0.25 … 2.5 mm² / 24 … 14 AWG
Strip length
8 … 9 mm / 0.31 … 0.35 inches

Physical Data

Width
12 mm / 0.472 inches
Height
100 mm / 3.937 inches
Depth
67.8 mm / 2.669 inches
Depth from upper-edge of DIN-rail
60.6 mm / 2.386 inches

Material Data

Color
Dark gray
Housing material
Polycarbonate; polyamide 6.6
Fire load
0.974 MJ
Weight
82.477 g
Conformity marking
CE

Technical Data

Number of analog inputs
4
Total number of channels (module)
4
Signal type
Voltage || Current
Signal type (current)
0 … 20 mADC; 4 … 20 mADC; 3.6 … 21 mADC; -20 … +20 mADC
Signal type (voltage)
0 … 10 VDC; -10 … +10 VDC; -0.2 … +0.2 VDC
Signal type (configurable)
Yes
Sensor connection
4 x (2-wire)
Input filter
50 Hz; 60 Hz; filter off
Input voltage (max.)
31.2 VDC
Signal characteristics
Differential
Diagnostics
Measurement range overflow/underflow; wire break in operating mode 4 … 20 mA and 3.6 … 21 mA NE43; overload in operating mode 0 … 20 mA, 4 … 20 mA, ±20 mA, 3.6 … 21 mA NE43
Resolution [bit]
16 bits
Input resistance (max.)
120 Ω
Data width
4 x 16-bit data; 4 x 8-bit control/status (optional)
Internal resistance
100 kΩ
Conversion time (typ.)
10 ms
Conversion time
Exception: The ±200 mV measurement range has a conversion time of 10 s and is therefore only suitable for slow systems.
Reference for measurement error
Input ranges
Measurement error (reference temperature)
25 °C
Measurement error, deviation (max.) from the upper-range value
0.1 %
Reference for measurement error (2)
±200 mV
Measurement error, reference temperature (2)
25 °C
Measurement error, deviation (max.) of the upper-range value (2)
0.3 %
Temperature error (max.) of the upper-range value
0.01 %/K
Supply voltage (system)
5 VDC; via data contacts
Current consumption (5 V system supply)
100 mA
Supply voltage (field)
24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact); Derating must be observed!
Isolation
Functional insulation: 2000 VDC system/channel; 2000 VDC channel/channel
Dielectric strength
510 VAC/775 VDC; per EN 60870-2-1
Indicators
LED (A-D) green: Function AI 1 … AI 4; LED (E-H) red: Error AI 1 … AI 4
Number of incoming power jumper contacts
2
Number of outgoing power jumper contacts
2
Current carrying capacity (power jumper contacts)
10 A
Derating
Derating (supply voltage): Ambient temperatures under laboratory conditions: (−25 … +30 %); for −40 … +55 °C: 24 V (−25 … +20 %); for +55 … +70 °C: 24 V (−25 … +10 %); Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple)

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0015

Commercial Data

Country of origin
DE
GTIN
4066966207804
Customs tariff number
85389099990