- Ambient temperature (operation)
- -40 … +70 °C
- Ambient temperature (storage)
- -40 … +85 °C
- Protection type
- IP20
- Pollution degree
- 2 per IEC 61131-2
- Operating altitude
- Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
- Mounting position
- Horizontal (standing/lying); vertical
- Relative humidity (without condensation)
- 95 %
- Relative humidity (with condensation)
- Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
- Vibration resistance
- Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
- Shock resistance
- Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
- EMC immunity to interference
- Per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
- EMC emission of interference
- Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
- Exposure to pollutants
- Per IEC 60068-2-42 and IEC 60068-2-43
- Permissible H2S contaminant concentration at a relative humidity 75 %
- 10 ppm
- Permissible SO2 contaminant concentration at a relative humidity 75 %
- 25 ppm