Wago

750-838/040-000

Controller CANopen; 640/832 KB Program/RAM; D-Sub; Extreme
750-838/040-000
750-838/040-000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€572.00
1
Payment methods:
A total of 50 Parts In-Stock from 7 Distributors

Environmental Requirements

Ambient temperature (operation)
-40 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
Relative humidity (without condensation)
95 %
Relative humidity (with condensation)
Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Mounting position
Horizontal (standing/lying); vertical
Mounting type
DIN-35 rail
Vibration resistance
Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
Shock resistance
Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
EMC immunity to interference
Per EN 61000-6-1, -2, EN 61131-2, marine applications, EN 50121-3-2, -4, -5, EN 60255-26
EMC emission of interference
Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Fire load
2.180 MJ
Permissible H2S contaminant concentration at a relative humidity 75 %
10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %
25 ppm

Connection Data

Connection technology: communication/fieldbus
CANopen: 1 x D-sub 9 plug
Connection technology: system supply
2 x CAGE CLAMP®
Connection technology: field supply
4 x CAGE CLAMP®
Connection type 1
System/field supply
Solid conductor
0.25 … 2.5 mm² / 24 … 14 AWG
Fine-stranded conductor
0.25 … 2.5 mm² / 24 … 14 AWG
Strip length
8 … 9 mm / 0.31 … 0.35 inches
Connection technology: device configuration
1 x Male connector; 4-pole

Physical Data

Width
50.5 mm / 1.988 inches
Height
100 mm / 3.937 inches
Depth
71.1 mm / 2.799 inches
Depth from upper-edge of DIN-rail
63.9 mm / 2.516 inches

Technical Data

Communication
CANopen
Visualization
None
CPU
32 bits
Programming languages per IEC 61131-3
Instruction List (IL) || Ladder Diagram (LD) || Function Block Diagram (FBD) || Continuous Function Chart (CFC) || Structured Text (ST) || Sequential Function Chart (SFC)
Programming environment
WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
Configuration options
EDS device description file || WAGO-I/O-CHECK
Cycle time
< 3 ms for 1000 bit instructions/256 digital I/O
Baud rate
10 kBd … 1 MBd
Bus segment length (max.)
1000 m
Transmission medium (communication/fieldbus)
Shielded Cu cable 3 x 0.25 mm²
Number of fieldbus nodes on master (max.)
110
Program memory
640 KB
Data memory
832 KB
Non-volatile software memory
8 KB
Memory for fieldbus input variables (max.)
512 bytes
Memory for fieldbus output variables (max.)
512 bytes
Number of modules per node (max.)
64
Number of PDOs
32 Tx / 32 Rx
Number of SDOs
2 SDO servers / 16 SDO clients
Input and output process image (fieldbus) max.
512 bytes/512 bytes
Other CANopen features
NMT slave || Minimum boot-up || Variable PDO mapping || Emergency message || Life guarding/heartbeat || Empty module configuration
COB ID distribution
SDO, standard
Node ID distribution
DIP switch
Supported profiles
Communication profile: DS-301 V4.01; device profile: DS-401 V2.0; limit monitoring, flank-triggered PDOs, configurable response in the event of an error, DSP 405, NMT master programmable using function blocks
Indicators
LED (STOP) red: Device/node Stop; LED (RUN) green: Initialization; LED (TX, RX OVERFLOW) red: CAN send/receive buffer overflow; LED (I/O, USR) red/green/orange: Local status, status programmable by user; LED (A, B) green: System power supply status, field supply
Derating
Total current for system supply: 1650 mA (ambient (operating) temperature < 60 °C; 1250 mA (ambient (operating) temperature: 60 … 70 °C); Derating (supply voltage): Ambient temperatures under laboratory conditions: (−25 … +30 %); for −40 … +55 °C: 24 V (−25 … +20 %); for +55 … +70 °C: 24 V (−25 … +10 %); Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple)
Supply voltage (system)
24 VDC; via pluggable connector (CAGE CLAMP® connection); Derating must be observed!
Input current (typ.) at nominal load (24 V)
500 mA
Power supply efficiency (typ.) at nominal load (24 V)
90 %
Current consumption (5 V system supply)
350 mA
Total current (system supply)
1650 mA
Supply voltage (field)
24 VDC; Power supply via pluggable connector (CAGE CLAMP® connection); Transmission via power jumper contacts; Derating must be observed!
Current carrying capacity (power jumper contacts)
10 A
Number of outgoing power jumper contacts
2
Ratings per
IEC/EN 60664-1
Rated surge voltage
1 kV

Mechanical Data

Weight
182.000 g
Color
Dark gray
Housing material
Polycarbonate; polyamide 6.6
Conformity marking
CE

Specifications

Product Group Code
0015

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4050821460152
Customs tariff number
85371091990

Notes

Note
Note: Configuration files required (EDS)!The EDS files can be downloaded for free at www.wago.com.