Wago

753-667/000-004

Electronics unit, fail-safe, 4/4 channel digital input/output; 24 VDC; 2 A; PROFIsafe
753-667/000-004
753-667/000-004
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€466.00
1
Payment methods:
A total of 352 Parts In-Stock from 12 Distributors

Environmental Requirements

Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-25 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
0 … 2000 m / 0 … 6562 ft
Mounting position
Horizontal (standing/lying); vertical
Relative humidity (without condensation)
95 %
Vibration resistance
4g per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
Per EN 61000-6-2, marine applications, EN 61000-6-7 (FS)
EMC emission of interference
Per EN 61000-6-3, -4; marine applications
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %
10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %
25 ppm

Connection Data

Connection technology: inputs/outputs
16 x CAGE CLAMP®
Connection type 1
Inputs/outputs
Solid conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches

Physical Data

Width
24 mm / 0.945 inches
Height
100 mm / 3.937 inches
Depth
67.8 mm / 2.669 inches
Depth from upper-edge of DIN-rail
60.6 mm / 2.386 inches

Material Data

Housing material
Polycarbonate; polyamide 6.6
Fire load
1.631 MJ
Weight
86.413 g
Conformity marking
CE

Functional Safety

Achievable safety classes
SIL 3; Category 4, PLe (two-channel); SIL 2; Category 2; PLd (one-channel)
Safety standards
IEC 61508-1 … -7; EN ISO 13849-1; EN 62061
Interface types according to ZVEI (inputs)
Drain; A, C0, C1, C2, C3
Interface types according to ZVEI (outputs)
Source; C0, C1, C2, C3, D0, D1, D2, D3
Test pulse duration (max.)
500 ms
Test pulse duration (min.)
0 ms

Technical Data

Number of digital inputs
4
Number of digital outputs
4
Total number of channels (module)
8
Signal type
Digital
Signal type (voltage)
24 VDC
Sensor connection
4 x (Fail-safe input with test pulse)
Actuator connection
4 x (fail-safe output with test pulse)
Input characteristic
Clock sensitive || Type 1 per IEC 61131
Input current per channel for signal (1) typ.
3.0 mA
Output circuit design
Power outputs
Output current per channel
2 A
Output current (module)
8 A
Output current
Short-circuit-protected
Switching frequency (max.)
50 Hz; Resistive load
Switching frequency (max.) (2)
0.1 Hz; Inductive load
Capacitive load for each channel
O1 … O4; 47 μ F
Signal frequency (max.)
50 Hz
Load type of switching frequency
Resistive load
Configuration options
PROFIsafe address adjustable via DIP switch or engineering software
Supply voltage (system)
5 VDC; via data contacts
Current consumption (5 V system supply)
120 mA
Supply voltage (field)
24 VSELV/PELV DC (-25 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)
Current consumption, field supply (module with no external load)
35 mA
Indicators
LED (A-D) green/red: Status/Error I1 … I4; LED (I-M) green/red: Status/error O1 … O4; LED (E) red: Group error; LED (F-H) green/red: Diagnostics
Number of incoming power jumper contacts
2
Number of outgoing power jumper contacts
2
Current carrying capacity (power jumper contacts)
10 A

Mechanical Data

Mounting type
DIN-35 rail
Pluggable connector
Pluggable

Specifications

Product Group Code
0015

Commercial Data

Country of origin
DE
GTIN
4066966213430
Customs tariff number
85340019000

Notes

Note
Pluggable connectors and coding fingers (753 Series) are not included.