Wago

787-1011

EPSITRON® COMPACT power supply; single-phase; output voltage 12 VDC; 4 A
787-1011
787-1011
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
£92.97
1
Payment methods:
A total of 7 Parts In-Stock from 11 Distributors

Safety And Protection

Isolation voltage (pri.-sec.)
DC 4.242 kV
Protection class
II
Protection type
IP20; per EN 60529
Resistance to reverse feed
≤ DC 25 V
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
≤ 30 VDC (in the event of a fault)
Short-circuit-protected
Yes
Open-circuit-proof
Yes
Parallel operation
Yes
Series operation
Yes
MTBF
> 500,000 h (per IEC 61709)

Environmental Requirements

Ambient temperature (operation)
-25 … +60 °C (Device starts at −40 °C (type-tested))
Ambient temperature (storage)
-25 … +80 °C
Ambient temperature UL (operation at UN)
-25 … +55 °C
Relative humidity
5 … 96 % (no condensation permissible)
Derating
−3 %/K (> 45 °C)

Connection Data

Connection type 1
Input/output
Connection technology
CAGE CLAMP®
WAGO connector
WAGO 740 Series
Solid conductor
0.08 … 2.5 mm² / 28 … 12 AWG
Fine-stranded conductor
0.08 … 2.5 mm² / 28 … 12 AWG
Strip length
6 … 7 mm / 0.24 … 0.28 inches

Signaling And Communication

Signaling
1 x Status indication LED (green)
Operation status indicator
Green LED (Uo)

Physical Data

Width
72 mm / 2.835 inches
Height
89 mm / 3.504 inches
Depth
59 mm / 2.323 inches
Depth from upper-edge of DIN-rail
55 mm / 2.165 inches

Material Data

Flammability class per UL94
V0
Fire load
0.000 MJ
Weight
255.000 g

Input

Phases
1
Nominal input voltage Ui nom
1 x AC 100 … 240 V
Input voltage range
1 x AC 85 … 264 V; DC 120 … 300 V
Input voltage derating
Io ≤ 3.5 A (< 100 VAC)
Nominal mains frequency range
44 … 66 Hz; 0 Hz
Input current Ii
≤ 0.5 A (230 VAC); ≤ 0.9 A (110 VAC)
Discharge current
≤ 1 mA
Inrush current
≤ 30 A (NTC)
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 80 ms (230 VAC); ≥ 10 ms (110 VAC)

Output

Nominal output voltage Uo nom
DC 12 V (SELV)
Output voltage range
DC 10.5 … 15.5 V (adjustable)
Default setting
DC 12 V
Nominal output current Io nom
4 A (12 VDC); 2.4 A (in any mounting position)
Nominal output power
48 W
Deviation
≤ 2 %
Residual ripple
≤ 100 mV (peak-to-peak)
Current limitation
1.1 x Io nom (typ.)
Overload behavior
Constant current

Standards And Specifications

Conformity marking
CE
Standards/specifications
EN 61010-1 || EN 61010-2-201 || EN 61204-3 || UL 60950-1 || UL 508 || DNV

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4050821297604
Customs tariff number
85044083900

Efficiency/Power Losses

Power loss Pl
≤ 2.2 W; ≤ 8.5 W (230 VAC; nominal load)
Power loss (max.) Pl (max.)
9 W (100 VAC / 12 VDC; 4 A)
Efficiency (typ.)
85 %

<B>Circuit Protection</B>

Internal fuse
T 2 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A (C characteristic), 10 A (B characteristic) or higher