Wago

787-1211

Switched-mode power supply; Compact; 1-phase; 12 VDC output voltage; 5 A output current; DC-OK LED
787-1211
787-1211
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 51 Parts In-Stock from 9 Distributors
Offer with manufacturer lead time
Ships in:On Request
Best price:
€26.33

Additional Information

Part Number
787-1211
UPC
4055143804226
Tariff Code
85044082900
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : DC-power supply
Class Code : EC002540
Version : 7

Safety And Protection

Isolation voltage (pri.-sec.)
DC 4.242 kV
Isolation voltage (pri.-PE)
DC 2.12 kV
Protection class
I
Protection type
IP20; per EN 60529
Reverse voltage protection
Yes
Resistance to reverse feed
≤ DC 16 V
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
≤ 20 VDC (in the event of a fault)
Short-circuit-protected
Yes
Open-circuit-proof
Yes
Parallel operation
Yes, for devices of the same type
Series operation
Yes, for 2 devices of the same type
MTBF
> 500,000 h (per IEC 61709)

Environmental Requirements

Ambient temperature (operation)
-25 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Relative humidity
20 … 90 % (no condensation permissible)
Derating
−3 %/K (> +45 °C and Ue = 90 VAC); −2.3 %/K (> +50 °C and Ue = 230 VAC)

Connection Data

Connection type 1
Input/output
Connection technology
Push-in CAGE CLAMP®
WAGO connector
picoMAX® 5.0, WAGO 2092 Series
Solid conductor
0.2 … 2.5 mm² / 24 … 12 AWG
Fine-stranded conductor
0.2 … 2.5 mm² / 24 … 12 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches
Cable length (max.)
30 m

Signaling And Communication

Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (Uo)

Physical Data

Width
72 mm / 2.835 inches
Height
90 mm / 3.543 inches
Depth
56 mm / 2.205 inches
Depth from upper-edge of DIN-rail
52.5 mm / 2.067 inches
Note (dimensions)
Depth: 48 mm (without cover)

Material Data

Flammability class per UL94
V0
Fire load
0.000 MJ
Weight
63.000 g

Input

Phases
1
Nominal input voltage Ui nom
1 x AC 100 … 240 V; DC 140 … 340 V
Input voltage range
1 x AC 85 … 264 V; DC 125 … 375 V
Input voltage derating
-2 %/V (< 100 VAC); -1.33 %/V (< 140 VDC)
Nominal mains frequency range
47 … 63 Hz; 0 Hz
Input current Ii
≤ 0.6 A
Discharge current
≤ 0.25 mA
Inrush current
≤ 30 A (NTC)
Power factor
≥ 0.5
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 600 ms (230 VAC); ≥ 12 ms (110 VAC)

Output

Nominal output voltage Uo nom
DC 12 V (SELV)
Output voltage range
DC 10 … 14 V (adjustable)
Default setting
DC 12 V
Nominal output current Io nom
5 A
Nominal output power
60 W
Deviation
≤ 1 %
Deviation, dynamic load change 10 … 90 %
≤ 1 %
Residual ripple
≤ 100 mV (peak-to-peak)
Overload behavior
Constant power (in overload range: 1.22 … 1.7 x Io nom); Hiccup in the event of a short circuit or permanent overload

Standards And Specifications

Conformity marking
CE
Standards/specifications
EN 61204-3 || EN 60335-1 || EN 62368-1 || UL 60950-1 || UL 508

Mechanical Data

Mounting type
DIN-35 rail || Screw mount (back/side)

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Box
Country of origin
CN
GTIN
4055143804226
Customs tariff number
85044083900

Efficiency/Power Losses

Power loss Pl
≤ 0.6 W
Power loss (max.) Pl (max.)
9 W (100 VAC / 12 VDC; 2.5 A)
Efficiency (typ.)
88.5 % (230 VAC; nominal load); 87.5 % (110 VAC; nominal load)

<B>Circuit Protection</B>

Internal fuse
T 3.15 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A or higher; Tripping characteristic: B

Related products