Safety And Protection

Rated voltage
250 V
Rated surge voltage
4 kV
Pollution degree
3
Dielectric strength (control/load circuit) (AC, 1 min)
5 kVrms
Dielectric strength (open contact) (AC, 1 min)
1 kVrms
Dielectric strength (load/load circuit) (AC, 1 min)
2.5 kVrms
Safety information
A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.
Protection type
IP20

Load Circuit

Number of changeover/switchover contacts
2
Contact material (relay)
AgNi + Au
Limiting continuous current
8 A
Switching voltage (max.)
AC 250 V
Switching power (resistive) max.
AC 2000 VA; DC (see load limit curve)
Switching capacity
AC-15: 3 A / AC 250 V; DC-13: 2 A / DC 24 V
Recommended minimum load
5 V / 2 mA / 50 mW
Pull-in time (typ.)
7 ms
Drop-out time (typ.)
3 ms
Bounce time (typ.)
6 ms
Electrical life (NO; resistive load; 23 °C)
1 x 10³ switching operations
Mechanical life
30 x 10⁶ switching operations
Switching frequency with/without load (max.)
10 min-1 / 1200 min-1

Environmental Requirements

Ambient temperature (operation at UN)
-40 … +70 °C
Ambient temperature (storage)
-40 … +70 °C
Processing temperature
-25 … +50 °C
Temperature range of connection cable
≥ (Tambient + 20 K)

Connection Data

Connection technology
Push-in CAGE CLAMP®
Solid conductor
0.34 … 2.5 mm² / 22 … 14 AWG
Fine-stranded conductor
0.34 … 2.5 mm² / 22 … 14 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches

Control Circuit

Nominal input voltage UN
DC 48 V
Input voltage range
±10 %
Nominal input current at UN
9 mA

Physical Data

Width
15 mm / 0.591 inches
Height
86 mm / 3.386 inches
Depth from upper-edge of DIN-rail
54 mm / 2.126 inches

Material Data

Color
Gray
Fire load
0.667 MJ
Weight
45.227 g

Standards And Specifications

Standards/specifications
EN 61010-2-201 || EN 61810-1 || EN 61373

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4050821292449
Customs tariff number
85364900990

Notes

Safety information
A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.
Note
Reinforced insulation between coil and contactsTo prevent damaging the gold layer, 30 VDC switching voltages and 50 mA currents must not be exceeded. Higher switching power eventually evaporates the gold layer. The resulting deposits in the housing may reduce service life.To protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit.

Signaling

Status indicator
Red LED

Related products