Wago

855-5005/500-001

Split-core current transformer; Primary rated current: 500 A; Secondary rated current: 5 A; Rated power: 0.5 VA; Accuracy class: 1
855-5005/500-001
855-5005/500-001
855-5005/500-001
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:

Environmental Requirements

Ambient temperature (operation)
-10 … +55 °C
Ambient temperature (storage)
-20 … +70 °C
Relative humidity
5 … 85 % (without condensation)
Operating altitude (max.)
2000 m

Connection Data

Feedthrough for measurement conductor
Ø 42 mm
Cable type
2 x 1.5 mm²; fine-stranded
Color code
Black = S1; red = S2

Physical Data

Cable length
3 m

Measurement Error

Accuracy class
1

Material Data

Flammability class per UL94
V2
Fire load
0.000 MJ
Weight
537.000 g

Input Current Transformers

Primary rated current
500 A
Rated continuous thermal current Icth
100 %
Rated short-time thermal current Ith
60 x IN / 1 s
Rated surge current Idyn
2.5 x Ith
Rated frequency
50 … 60 Hz

Output (Current Transformer)

Secondary rated current
5 A
Rated power Sr
0.5 VA

Standards And Specifications

Conformity marking
CE
Standards/specifications
EN 61869-1 || EN 61869-2

Mechanical Data

Mounting type
Split-core current transformer (suspended)

Specifications

Product Group Code
0029

Commercial Data

Packaging type
Box
Country of origin
NL
GTIN
4055143950817
Customs tariff number
85043180888

Test Voltage

Test voltage
AC 3 kV; 50 Hz; 1 min

Related products