Wago

857-359

Relay module; Nominal input voltage: 24 … 230 V AC/DC; 1 changeover contact; Limiting continuous current: 6 A; Yellow status indicator; Module width: 6 mm
857-359
857-359
857-359
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€22.93
1
Payment methods:
A total of 165 Parts In-Stock from 10 Distributors

Basic Relay

WAGO Basic Relay
857-150

Safety And Protection

Rated voltage
300 V
Rated surge voltage
4 kV
Type of circuits
Mains circuits
Overvoltage category
III
Pollution degree
2
Dielectric strength (control/load circuit) (AC, 1 min)
3.51 kVrms
Dielectric strength (open contact) (AC, 1 min)
1 kVrms
Insulation type (control/load circuit)
Reinforced insulation (safe isolation)
Insulation type (between adjacent devices of the same type)
Double insulation (safe isolation)
Insulation type (to adjacent devices of different types)
Basic insulation
Safety information
Adjacent devices are devices of the same design (series) that are arranged next to each other with the same orientation on the mounting rail. An end stop (249-116) must be fitted to devices of other types for compliance with the reinforced insulation requirements.
Protection type
IP20

Load Circuit

Number of changeover/switchover contacts
1
Contact material (relay)
AgSnO2
Limiting continuous current
6 A
Inrush current (resistive) max.
(AC) 20 A / 0.02 s
Switching voltage (max.)
AC 250 V
Switching power (resistive) max.
AC 1500 VA; DC (see load limit curve)
Switching capacity
AC-15: 3 A / AC 250 V; DC-13: 2 A / DC 24 V
Recommended minimum load
10 V / 10 mA; 24 V / 1 mA
Pull-in time (typ.)
15 ms
Drop-out time (typ.)
25 ms
Bounce time (typ.)
3.5 ms
Electrical life (NO; resistive load; 23 °C)
50 x 10³ switching operations
Mechanical life
5 x 10⁶ switching operations
Switching frequency with/without load (max.)
6 min-1 / 60 min-1

Environmental Requirements

Ambient temperature (operation at UN)
-25 … +70 °C
Ambient temperature (storage)
-40 … +70 °C
Processing temperature
-25 … +50 °C
Temperature range of connection cable
≥ (Tambient + 30 K)
Relative humidity
5 … 85 % (no condensation permissible)
Operating altitude (max.)
2000 m

Connection Data

Connection technology
Push-in CAGE CLAMP®
Solid conductor
0.34 … 2.5 mm² / 22 … 14 AWG
Fine-stranded conductor
0.34 … 2.5 mm² / 22 … 14 AWG
Fine-stranded conductor; with insulated ferrule
0.34 … 1.5 mm² / 22 … 16 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches

Control Circuit

Nominal input voltage UN
AC/DC 24 … 230 V
Input voltage range
-30 … +10 %
Nominal input current at UN
4 mA (230 VAC); 20 mA (24 VDC)
Nominal frequency range (input voltage)
50 … 60 HzAC / 0 HzDC

Physical Data

Width
6 mm / 0.236 inches
Height
94 mm / 3.701 inches
Depth from upper-edge of DIN-rail
81 mm / 3.189 inches

Material Data

Fire load
0.552 MJ
Weight
30.877 g

Standards And Specifications

Standards/specifications
EN 50121-3-2 || EN 61010-2-201 || EN 61810-1 || EN 61373 || EN 61000-6-2 || EN 61000-6-3 || EN 50121-3 || UL 508

Mechanical Data

Mounting type
DIN-35 rail
Mounting position
Horizontal (standing/lying); vertical

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4050821856689
Customs tariff number
85364900990

Notes

Safety information
Adjacent devices are devices of the same design (series) that are arranged next to each other with the same orientation on the mounting rail. An end stop (249-116) must be fitted to devices of other types for compliance with the reinforced insulation requirements.
Note
To protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit.

Signaling

Status indicator
Yellow LED