Wago

857-451

JUMPFLEX® signal conditioner; passive isolator; 1-channel
857-451
857-451
857-451
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 16 Parts In-Stock from 11 Distributors
Offer with manufacturer lead time
Ships in:On Request
Best price:
€104.56

Additional Information

Part Number
857-451
UPC
4045454471323
Tariff Code
85437090300
ETIM
Group Code : EG000026
Group Description : Sensors
Class Description : Isolation amplifier
Class Code : EC002653
Version : 7

Output (Analog)

Output signal type
Current
Output signal (current)
0 … 20 mA; 4 … 20 mA
Load impedance (current output)
≤ 600 ΩTemperature range restrictions may occur.

Output (Voltage Tap)

Voltage drop
≤ 2.5 V (at 20 mA (output))

Signal Processing

Limit frequency
100 Hz
Step response (typ.)
3.5 ms

Configuration

Configuration options
Pre-configured

Environmental Requirements

Ambient temperature (operation)
-25 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Temperature range of connection cable
≥ (Tambient + 15 K)
Temperature range of connection cable (UL)
70 °C
Relative humidity
5 … 95 % (no condensation permissible)
Operating altitude (max.)
2000 m

Connection Data

Connection technology
Push-in CAGE CLAMP®
Solid conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.34 … 2.5 mm² / 22 … 14 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches
Cable type
Shielded cable

Signaling And Communication

Configuration options
Pre-configured

Supply

Power supply type
Passive (via input)

Physical Data

Width
6 mm / 0.236 inches
Height
94 mm / 3.701 inches
Depth from upper-edge of DIN-rail
97.8 mm / 3.85 inches

Measurement Error

Transmission error (typ.)
≤ 0.1 % of upper-range value
Load error
≤ 0.05 % (of upper-range value; per 100 Ω load)
Temperature coefficient
≤ 0.01 %/K

Material Data

Fire load
0.598 MJ
Weight
34.200 g

Input

Input signal type
Current
Input signal (current)
0 … 20 mA; 4 … 20 mA
Input current (max.)
40 mA
Input voltage (max.)
20 V
Response threshold
200 µA

Insulation Parameters(Ul)

Insulation type (input/analog output)
Reinforced insulation (safe isolation)

Standards And Specifications

Conformity marking
CE
EMC immunity to interference
EN 61000-6-2
EMC emission of interference
EN 61000-6-3
Standards/specifications
EN 61010-1 || DNV

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Bag
Country of origin
DE
GTIN
4045454471323
Customs tariff number
85437090300

Notes

Safety information
Outputs must not be left open!
Note
Use shielded signal lines!Only use shielded signal lines for analog input and output signals.Only then can you ensure that the accuracy and interference immunity specified for the device can be achieved, even in the presence of interference acting on the signal cable.

Test Voltage

Test voltage (input/output)
AC 3 kV; 50 Hz; 1 min