Wago

857-812

JUMPFLEX® signal conditioner; temperature; thermocouples of type K S, B, and R; configurable
857-812
857-812
857-812
857-812
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 1 Part In-Stock from 6 Distributors

Additional Information

Part Number
857-812
UPC
4050821255291
Tariff Code
85437090300
ETIM
Group Code : EG000026
Group Description : Sensors
Class Description : Temperature transmitter
Class Code : EC002919
Version : 7

Output (Analog)

Output signal type
Current || Voltage
Output signal (voltage)
0 … 5 V; 1 … 5 V; 0 … 10 V; 2 … 10 V
Output signal (current)
0 … 10 mA; 2 … 10 mA; 0 … 20 mA; 4 … 20 mA
Load impedance (voltage output)
≥ 2 kΩ
Load impedance (current output)
≤ 600 Ω

Input (Tc Sensors)

Sensor types (TC)
Type K || Type S || Type B || Type R
Temperature measurement range (TC)
0 … 1200 °C (Type K); 0 … 1600 °C (Type S); 600 … 1800 °C (Type B); 0 … 1600 °C (Type R)
Cold junction compensation
ON/OFF (default: ON)
Cold junction error
3 K (typ. 2 K )

Signal Processing

Step response (typ.)
60 ms (cold junction compensation (Off)); 120 ms (cold junction compensation (ON))

Configuration

Configuration options
DIP switch

Environmental Requirements

Ambient temperature (operation)
-25 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Relative humidity
5 … 95 % (no condensation permissible)
Operating altitude (max.)
2000 m

Connection Data

Connection technology
Push-in CAGE CLAMP®
Solid conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.34 … 2.5 mm² / 22 … 14 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches

Signaling And Communication

Configuration options
DIP switch

Supply

Power supply type
24 VDC
Nominal supply voltage US
DC 24 V
Supply voltage range
±30 %
Current consumption at nominal supply voltage
≤ 40 mA

Physical Data

Width
6 mm / 0.236 inches
Height
94 mm / 3.701 inches
Depth from upper-edge of DIN-rail
97.8 mm / 3.85 inches

Measurement Error

Transmission error (typ.)
≤ 0.1 % at full measurement span
Transmission error for the set measurement range
≤ (150 K/set measurement range [K]) %
Temperature coefficient
≤ 0.04 %/K

Material Data

Fire load
0.420 MJ
Weight
35.700 g

Input

Input signal type
TC sensors

Standards And Specifications

Conformity marking
CE
EMC immunity to interference
EN 61000-6-2
EMC emission of interference
EN 61000-6-4

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Bag
Country of origin
DE
GTIN
4050821255291
Customs tariff number
85437090300

Test Voltage

Test voltage (input/output/supply)
AC 2.5 kV; 50 Hz; 1 min

Related products