Wago

857-815

JUMPFLEX® signal conditioner; temperature; loop-powered RTD; configurable
857-815
857-815
857-815
857-815
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€223.92
1
Payment methods:
A total of 14 Parts In-Stock from 13 Distributors
Offer with manufacturer lead time
Ships in:On Request
Best price:
€164.23

Additional Information

Part Number
857-815
UPC
4055143475648
Tariff Code
85437090300
ETIM
Group Code : EG000026
Group Description : Sensors
Class Description : Temperature transmitter
Class Code : EC002919
Version : 7

Output (Analog)

Output signal type
Current
Output signal (current)
4 … 20 mA; 20 … 4 mA
Load impedance (current output)
See derating graphic

Signal Processing

Step response (typ.)
1000 ms

Configuration

Configuration options
DIP switch

Environmental Requirements

Ambient temperature (operation)
-25 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Temperature range of connection cable
≥ (Tambient + 10 K)
Temperature range of connection cable (UL)
75 °C
Relative humidity
5 … 95 % (no condensation permissible)
Operating altitude (max.)
2000 m

Connection Data

Connection technology
Push-in CAGE CLAMP®
Solid conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.34 … 2.5 mm² / 22 … 14 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches

Signaling And Communication

Configuration options
DIP switch

Input (Rtd Sensors)

Sensor types (RTD)
Pt100 || Pt200 || Pt500 || Pt1000
Sensor connection
2-wire; 3-wire; 4-wire (switchable)
Sensor power supply (RTD) max.
≤ 0.5 mA
Temperature measurement range (RTD)
-200 … 850°C
Measurement span (RTD) min.
50 K

Supply

Power supply type
Loop-powered (via output)
Supply voltage
DC 8 … 30 V (Power is derived from the output circuit.)
Power loss (max.) Pl (max.)
0.7 W

Physical Data

Width
6 mm / 0.236 inches
Height
94 mm / 3.701 inches
Depth from upper-edge of DIN-rail
97.8 mm / 3.85 inches

Measurement Error

Transmission error (typ.)
≤ 0.1 % at full measurement span
Transmission error for the set measurement range
≤ ((40 K/set measurement range [K]) + 0.1) %
Transmission error (under interference)
≤ 5 %
Temperature coefficient
≤ 0.02 %/K

Material Data

Fire load
0.013 MJ
Weight
38.940 g

Input

Input signal type
Pt sensors || Resistance

Insulation Parameters(Ul)

Overvoltage category
II
Pollution degree
2
Insulation type (input/analog output)
Reinforced insulation (safe isolation)

Standards And Specifications

Conformity marking
CE
EMC immunity to interference
EN 61000-6-2; EN 61326-1; EN 50121-3-2
EMC emission of interference
EN 61000-6-3; EN 61326-1; EN 50121-3-2
Standards/specifications
EN 61010-1 || EN 61373 || EN 50121-3-2

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Bag
Country of origin
DE
GTIN
4055143475648
Customs tariff number
85437090300

Notes

Note
Use shielded signal lines!Only use shielded signal lines for analog input and output signals.Only then can you ensure that the accuracy and interference immunity specified for the device can be achieved, even in the presence of interference acting on the signal cable.

Test Voltage

Test voltage (input/analog output)
3 kVAC; 50 … 60 Hz; 1 min

Input (Resistors)

Input range (resistor)
0 … 1 kΩ; 0 … 4.5 kΩ