Weidmuller

1030600000

WDL 2.5/S/NT/L/PE
1030600000
1030600000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
£302.93
1
Payment methods:
A total of 115 Parts In-Stock from 11 Distributors
Offer with manufacturer lead time
Ships in:On Request
Best price:
€2.34

Additional Information

Part Number
1030600000

Approvals

Approvals
BBJ, CE, CSA, EAC, GERMLLOYD, NEMKO, UR
ROHS
Conform
UL File Number Search
E60693

Dimensions And Weights

Width
6.1 mm
Width (inches)
0.24 inch
Height
84.5 mm
Height (inches)
3.327 inch
Depth
48 mm
Depth (inches)
1.89 inch
Net weight
18.39 g

Csa Rating Data

Certificate No. (CSA)
12400-296
Current size B (CSA)
10 A
Current size D (CSA)
10 A
Voltage size B (CSA)
300 V
Voltage size D (CSA)
300 V
Wire cross section max. (CSA)
12 AWG
Wire cross section min. (CSA)
26 AWG

Additional Technical Data

Explosion-tested version
No
Number of similar terminals
1
Open sides
right
Type of mounting
Snap-on

Material Data

Material
Wemid
Colour
dark beige
UL 94 flammability rating
V-0

Safety Note

Safety notice
Safety Information

Classifications

ETIM 6.0
EC000897
ETIM 7.0
EC000897
EClass 9.0
27-14-11-20
EClass 9.1
27-14-11-20
EClass 10.0
27-14-11-20
UNSPSC
30-21-18-11

System Specifications

Version
Screw connection, NT, L and PE connection, with busbar connection 10x3, for plug-in cross-connector, One end without connector
End cover plate required
Yes
Number of potentials
3
Number of levels
3
Number of clamping points per level
2
Number of potentials per tier
1
Levels cross-connected internally
No
PE connection
Yes
Rail
TS 35
N-function
Yes
PE function
Yes
PEN function
No

Disconnect Terminals

For N-busbar
10 x 3 mm

Temperatures

Storage temperature, max.
40 °C
Storage temperature, min.
10 °C
Storage temperature
10 °C...40 °C
Continuous operating temp., min.
-50 °C
Continuous operating temp., max.
120 °C

Pe Rating Data

PEN function
No

Rating Data

Rated cross-section
2.5 mm²
Rated voltage
400 V
Rated current
24 A
Current at maximum wires
32 A
Standards
In accordance with IEC 60947-7-1
Volume resistance according to IEC 60947-7-x
1.33 mΩ
Power loss in accordance with IEC 60947-7-x
0.77 W
Rated impulse withstand voltage
4 kV
Pollution severity
3

Conductors For Clamping (Rated Connection)

Blade size
0.6 x 3.5 mm
Clamping range, max.
4 mm²
Clamping range, min.
0.13 mm²
Clamping screw
M 2.5
Connection cross-section, stranded, max.
4 mm²
Connection cross-section, stranded, min.
1.5 mm²
Connection direction
on side
Gauge to IEC 60947-1
A3
Number of connections
5
Stripping length
8 mm
Tightening torque, max.
0.6 Nm
Tightening torque, min.
0.4 Nm
Torque level with DMS electric screwdriver
1
Type of connection
Screw connection
Wire connection cross section AWG, max.
AWG 12
Wire connection cross section AWG, min.
AWG 26
Wire connection cross section, finely stranded, max.
4 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, max.
2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, min.
0.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max.
2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min.
0.25 mm²
Wire connection cross-section, finely stranded, min.
0.5 mm²
Wire connection cross-section, solid core, max.
4 mm²
Wire connection cross-section, solid core, min.
0.5 mm²

Ul Rating Data

Certificate No. (UR)
E60693
Conductor size Factory wiring max. (UR)
12 AWG
Conductor size Factory wiring min. (UR)
26 AWG
Conductor size Field wiring max. (UR)
12 AWG
Conductor size Field wiring min. (UR)
22 AWG
Current size C (UR)
15 A
Voltage size C (UR)
300 V