Description
Surge protection for instrumentation and control, 48 V, 68 V, 300 mA, IEC61643-21:2009, DIN EN 60079-0.2009, DIN EN 60079-26:2007, DIN EN 61241-11:2006, HART-compatible- Part Number
- 1063820000
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Further Details Of Approvals
- GOST certificate
- GOST-Zertifikat
Protection Ex - Data
- ATEX - dust labelling
- II 1 D Ex ia IIIC T135 °C …T85 °C Da
- ATEX - gas labelling
- II 1 G Ex ia IIC T4… T6 Ga
- IECEx - dust labelling
- II 1 D Ex ia IIIC T135 °C …T85 °C Da
- IECEx - gas labelling
- II 1 G Ex ia IIC T4… T6 Ga
- Input power, max. P
- 0.75 W
- Input voltage, max. U
- 55 V
- Internal capacity, max. C
- 1 nF
- Internal inductance, max. L
- 0 µH
- Temperature class T4/135°C (-40°C ... +120 °C) li
- 300 mA
- Temperature class T5/100°C (-40 ° C ... +85 °C) li
- 300 mA
- Temperature class T6/85 °C (-40 °C ... +70 °C) li
- 300 mA
General Data
- Colour
- Light Blue
- Design
- Terminal
- Isolating function
- No
- Optical function display
- No
- Protection degree
- IP20
- Rail
- TS 35
- Segment
- Measurement - Monitoring - Setting
- UL 94 flammability rating
- V-0
- Version
- Surge protection for measurement and control
Probability Of Failure
- Λges
- 29
- MTTF
- 3,936 years
- PFH in 1*10
- 1.95
- SFF
- 93.28 %
- SIL PAPER
- SIL Paper
- SIL in compliance with IEC 61508
- 3
Approvals
- Approvals
- CE, CSAEX, DEKRAATEX, EAC, FUSAFETY, IECEXDEK
- ROHS
- Conform
Insulation Coordination Acc. To En 50178
- Pollution severity
- 2
- Surge voltage category
- III
Rated Data Iec / En
- Dielectric strength at FG against PE
- ≥ 500 V
- Discharge current I
- 2.5 kA
- Discharge current, max. (8/20 µs)
- 10 kA
- Input voltage, max. U
- 55 V
- Insertion loss
- 5.34 MHz
- Lightning test current I
- 0.5 kA
- Lightning test current, I
- 0.5 kA
- Max. continuous voltage, Uc (AC)
- 60 V
- Max. continuous voltage, Uc (DC)
- 85 V
- Number of poles
- 1
- Overload - failure mode
- Modus 2
- Protection level U
- ≤ 2000 V
- Pulse-reset capacity
- ≤ 15 ms
- Rated current I
- 300 mA
- Rated voltage (AC)
- 48 V
- Rated voltage (DC)
- 68 V
- Requirements category acc. to IEC 61643-21
- C2, C3, D1
- Signal transmission properties (-3 dB)
- 5 Mhz
- Standards
- IEC61643-21:2009, DIN EN 60079-0.2009, DIN EN 60079-26:2007, DIN EN 61241-11:2006, HART-compatible
- Surge current-carrying capacity C2
- 2.5 kA 8/20 µs 5 kV 1.2/50 µs
- Surge current-carrying capacity C3
- 50 A 10/1000 μs
- Surge current-carrying capacity D1
- 0.5 kA 10/350 μs
- Voltage type
- AC/DC
- Volume resistance
- 1.8 Ω 10 %
Dimensions And Weights
- Width
- 12.4 mm
- Width (inches)
- 0.488 inch
- Height
- 76 mm
- Height (inches)
- 2.992 inch
- Depth
- 58.5 mm
- Depth (inches)
- 2.303 inch
- Net weight
- 39.8 g
Csa Protection Data
- Gas group C
- IIB
- Gas group D
- IIA
- Gas groups A, B
- IIC
- Input current, max. I
- 300 mA
- Input voltage, max. U
- 55 V
- Internal capacity, max. C
- 1 nF
- Internal inductance, max. L
- 0 µH
Connection Data
- Type of connection
- Screw connection
- Tightening torque, min.
- 0.5 Nm
- Tightening torque, max.
- 0.8 Nm
- Clamping range, min.
- 0.5 mm²
- Clamping range, max.
- 4 mm²
- Wire cross-section, solid, min.
- 0.5 mm²
- Wire cross-section, solid, max.
- 6 mm²
- Conductor cross-section, flexible, AEH (DIN 46228-1), min.
- 0.5 mm²
- Conductor cross-section, flexible, AEH (DIN 46228-1), max.
- 4 mm²
- Connection cross-section, stranded, min.
- 0.5 mm²
- Connection cross-section, stranded, max.
- 4 mm²
Tender Specification Sheets
- Long specification
- Surge protection in a one piece, 12.4 mm wide terminal rail module for an intrinsically safe, floating-ground signal circuit with 48 VDC in 2-wire technology. A current loop (Ex ia) with max. 0.3 A can be protected here. When the terminal is fitted, a sparkover gap is simultaneously created to the high-impedance earth between the terminal rail (earth) and the reference potential (ground) of the protective circuit. Optical identification of the terminal based on the type of protective circuit and the voltage level. The terminal can be labelled. Suitable for ATEX applications. Tested according to explosion protection types in EX areas: Ex ia IIC / Ex iaD.
- Short specification
- Surge protection in a one piece, 12.4 mm wide terminal rail module for an intrinsically safe, floating-ground signal circuit in 2-wire technology. Version: 48 VDC Suitable for ATEX applications
Classifications
- ETIM 6.0
- EC000943
- ETIM 7.0
- EC000943
- EClass 9.0
- 27-13-08-07
- EClass 9.1
- 27-13-08-07
- EClass 10.0
- 27-13-08-07
- UNSPSC
- 30-21-19-21
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Temperatures
- Humidity
- 5...96 %
- Operating temperature, max.
- 70 °C
- Operating temperature, min.
- -40 °C
- Storage temperature, max.
- 80 °C
- Storage temperature, min.
- -40 °C
- Operating temperature
- -40 °C...70 °C
- Storage temperature
- -40 °C...80 °C
Ratings Iecex/Atex/Cul
- ATEX certificate
- ATEX Certificate
- IEC Ex certificate
- IECEX Zertifikat
- CUL certificate
- cUL Certificate
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther