Weidmuller
1161150000
VSPC 4SL 12VAC EX
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Product Conditions:
Further Details Of Approvals
- GOST certificate
- GOST-Zertifikat
Protection Ex - Data
- ATEX - dust labelling
- II 1 D Ex ia IIIC T135 °C …T85 °C Da
- ATEX - gas labelling
- II 1 G Ex ia IIC T4… T6 Ga
- Certificate No. (ATEX)
- KEMA10ATEX0148X
- IECEx - dust labelling
- II 1 D Ex ia IIIC T135 °C …T85 °C Da
- IECEx - gas labelling
- II 1 G Ex ia IIC T4… T6 Ga
- Input power, max. P
- 3 W
- Input voltage, max. U
- 19 V
- Internal capacity, max. C
- < 4 nF
- Internal inductance, max. L
- 0 µH
- Temperature class T4/135°C (-40°C ... +85°C) li
- 350 mA
- Temperature class T5/100°C (-40 ° C ... +75°C) li
- 250 mA
- Temperature class T6/85 °C (-40 °C ... +60°C) li
- 250 mA
General Data
- Colour
- Light Blue
- Design
- Terminal, miscellaneous
- Optical function display
- No
- Protection degree
- IP20
- Segment
- Measurement - Monitoring - Setting
- UL 94 flammability rating
- V-0
- Version
- without warning function / function indicator
- Protected binary signals
- 4
Probability Of Failure
- Λges
- 45
- MTTF
- 2,537 Years
- PFH in 1*10
- 8.9
- SFF
- 79.3 %
- SIL PAPER
- SIL PAPER
- SIL in compliance with IEC 61508
- 2
Approvals
- Approvals
- CE, CSAEX, EAC, IECEXDEK, KEMAATEX
- ROHS
- Conform
Insulation Coordination Acc. To En 50178
- Pollution severity
- 2
- Surge voltage category
- III
Rated Data Iec / En
- Dielectric strength at FG against PE
- ≥ 500 V
- Discharge current I
- 2.5 kA
- Input voltage, max. U
- 19 V
- Lightning test current, I
- 2.5 kA
- Max. continuous voltage, Uc (AC)
- 13.2 V
- Max. continuous voltage, Uc (DC)
- 18 V
- Number of poles
- 2
- Overload - failure mode
- Modus 2
- Protection level U
- 250 V
- Protection level on output side Wire-PE 1kV/µs, typically
- 30 V
- Protection level on output side Wire-wire 1 kV/µs, typically
- 55 V
- Protection level on output side Wire-wire 8/20 µs, typically
- 55 V
- Protection level, U
- 55 V
- Pulse-reset capacity
- ≤ 20 ms
- Rated current I
- 300 mA
- Rated voltage (AC)
- 12 V
- Rated voltage (DC)
- 16 V
- Requirements category acc. to IEC 61643-21
- C1, C2, C3, D1
- Signal transmission properties (-3 dB)
- 2.5 MHz
- Signalling contact
- No
- Standards
- IEC 61643-21, IEC 62305, DIN EN 60079-0.2009, DIN EN 60079-11:2007, DIN EN 60079-26:2007, DIN EN 61241-11:2006
- Surge current-carrying capacity C1
- < 1 kA 8/20 μs
- Surge current-carrying capacity C2
- 5 kA 8/20 μs
- Surge current-carrying capacity C3
- 100 A 10/1000 μs
- Surge current-carrying capacity D1
- 2.5 kA 10/350 μs
- Voltage type
- AC
- Volume resistance
- 4.7 Ω
Dimensions And Weights
- Width
- 17.8 mm
- Width (inches)
- 0.701 inch
- Height
- 90 mm
- Height (inches)
- 3.543 inch
- Depth
- 69 mm
- Depth (inches)
- 2.717 inch
- Net weight
- 49 g
Csa Protection Data
- Gas group C
- IIB
- Gas group D
- IIA
- Gas groups A, B
- IIC
- Input voltage, max. U
- 19 V
- Internal capacity, max. C
- 4 nF
- Internal inductance, max. L
- 0 µH
Connection Data
- Type of connection
- Pluggable in VSPC BASE
Tender Specification Sheets
- Long specification
- Surge protection plug for use in connection with the base element VSPC BASE 4SL FG for four wires with a common ground. Two-stage protection circuit in the plug consisting of coarse protection, decoupling resistors and fine protection between the signal wires and the signal ground/ground/earth. Suitable for intrinsically safe powered signal cables EX ia. Mechanical identification of the plug to the base element according to the switching type and rated voltage. Protected plug with coding pin and counter-profile for the base element. Optical identification of the protected plug based on the type of protected switching and the voltage level. It is possible to mark the plug.
- Short specification
- Surge protection plugs for base element VSPC BASE 4SL FG, coarse and fine common mode voltage protection for four wires with a common signal ground for intrinsically safe signal cables EX ia. Version: 12 V AC
Classifications
- ETIM 6.0
- EC000943
- ETIM 7.0
- EC000943
- EClass 9.0
- 27-13-08-07
- EClass 9.1
- 27-13-08-07
- EClass 10.0
- 27-13-08-07
- UNSPSC
- 30-21-19-21
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Temperatures
- Humidity
- 5...96 %
- Operating temperature, max.
- 70 °C
- Operating temperature, min.
- -40 °C
- Storage temperature, max.
- 80 °C
- Storage temperature, min.
- -40 °C
- Operating temperature
- -40 °C...70 °C
- Storage temperature
- -40 °C...80 °C
Ratings Iecex/Atex/Cul
- ATEX certificate
- ATEX Certificate
- IEC Ex certificate
- IECEX Zertifikat
- Certificate No. (ATEX)
- KEMA10ATEX0148X
- CUL certificate
- cUL Certificate
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther