Weidmuller
1176000000
ACT20M-AI-AO-S
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
€199.19
1
Payment methods:
A total of 17 Parts In-Stock from 13 Distributors
Product Conditions:
Additional Information
- Part Number
- 1176000000
General Data
- Accuracy
- < 0.05 % of measuring range
- Configuration
- DIP switch
- Galvanic isolation
- 3-way isolator
- Power consumption, max.
- 1.2 W
- Power consumption, typ.
- 0.84 W
- Rail
- TS 35
- Step response time
- ≤ 7 ms
- Temperature coefficient
- ≤ 0.01 % / °C
- Voltage supply
- 24 V DC ± 30 %
Probability Of Failure
- MTBF
- 231 Years
Approvals
- Approvals
- CE, CULUS, DETNORVER, DNV GL, EAC, FMEX, IECEXKEM, KEMAATEX
- ROHS
- Conform
- UL File Number Search
- E337701
Dimensions And Weights
- Width
- 6.1 mm
- Width (inches)
- 0.24 inch
- Height
- 112.5 mm
- Height (inches)
- 4.429 inch
- Depth
- 114.3 mm
- Depth (inches)
- 4.5 inch
- Net weight
- 80 g
Connection Data
- Type of connection
- Screw connection
- Tightening torque, min.
- 0.4 Nm
- Tightening torque, max.
- 0.6 Nm
- Clamping range, rated connection
- 2.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, max.
- 2.5 mm²
- Wire connection cross section AWG, min.
- AWG 30
- Wire connection cross section AWG, max.
- AWG 14
Rated Data Ul
- UL certificate
- E337701.pdf
Tender Specification Sheets
- Long specification
- Universal standard signal isolating amplifier1-channel signal isolating amplifier in 6.1 mm width with external power supply,for transmitting and isolating analogue DC current signals 0/4 to 20 mA and voltage signals 0/2 to 10 V // 0/1 to 5 V.Add-on housing for TS35 rail mountingDimensions: L/W/H 114.3/ 6.1/ 112.5 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20 Input 0/4...20 mA 0/2...10 V or 0/1...10 VOutput 0/4...20 mA 0/2...10 V or 0/1...5 VLoad resistance < 600 Ohm/ Strom/> 10 kOhm/ voltageTransmission error < 0,05 % v. E. Limit frequency 100 HzAuxiliary power 24 VDC +/- 30 %Power loss approx. 0.8 WAmbient temperature range -25 °C...+70 °C Isolation EN 61010-1, 3-way isolation up to 2.5 kV AC/DC of all circuits against each otherTest voltage 2.5 kV input against output against auxiliary powerRated voltage 300 V AC/DC at overvoltage category II and pollution degree 2Approvals cULus, FM Div2, ATEX Zone2, DNV, GLType ACT20M-AI-AO-S
- Short specification
- Universal standard signal isolating amplifier1-channel signal isolating amplifier in 6.1 mm width with external power supply,for transmitting and isolating analogue DC current signals 0/4...20 mA and voltage signals0/2...10V // 0/1...5 V. I/O signals are configured with DIP switches.
Input
- Number of inputs
- 1
- Sensor
- Voltage source, Current source, 2-wire transmitter (without own power supply)
- Sensor supply
- 17…28 V DC (@ 20 mA)
- Input voltage
- configurable, 0(2)…10 V, 0(1)…5 V
- Input resistance, voltage
- >500 kΩ
- Input current
- configurable, 0...20 mA, 4…20mA
- Voltage drop, current input
- <1,5 V
- Input resistance, current
- 70 Ω
- Voltage drop
- <1,5 V
Classifications
- ETIM 6.0
- EC002653
- ETIM 7.0
- EC002653
- EClass 9.0
- 27-21-01-20
- EClass 9.1
- 27-21-01-20
- EClass 10.0
- 27-21-01-20
Output
- Number of outputs
- 1
- Output voltage, note
- configurable, 0(2)...10 V, 0(1)...5 V
- Output current
- configurable, 0...20 mA, 4...20 mA
- Cut-off frequency (-3 dB)
- 100 Hz
- Load impedance voltage
- ≥ 10 kΩ
- Load impedance current
- ≤ 600 Ω, @ max 23mA
Product Information
- Product information
- The configurable DC isolating amplifier ACT20M-AI-AO-S isolates and converts analogue standard signals. An analogue input signal is linearly converted into an analogue output signal and galvanically isolated. The input can also be operated as an active current loop (the loop current is supplied by the device). The power supply is galvanically isolated from the input and output (3-way isolation) by means of direct wiring or the Weidmüller rail bus. The configurable DC isolation amplifier ACT20M-AI-2AO-S offers the same functionality, but has 2 galvanically isolated outputs (4-way isolation).
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Data For Ex Applications (Atex)
- Marking
- II 3 G Ex nA IIC T4 Gc
Insulation Coordination
- EMC standards
- IEC 61326-1, NE 21
- Galvanic isolation
- 3-way isolator
- Insulation voltage
- 2.5 kVeff /1 min.
- Pollution severity
- 2
- Rated voltage
- 300 Veff
- Surge voltage category
- II
Temperatures
- Humidity
- 40 °C / 93 % rel. humidity, no condensation
- Operating temperature, max.
- 70 °C
- Operating temperature, min.
- -25 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -40 °C
- Operating temperature
- -25 °C...70 °C
- Ambient temperature
- -25 °C...+70 °C
- Storage temperature
- -40 °C...85 °C
Ratings Iecex/Atex/Cul
- Certificate No. (ATEX)
- KEMA10ATEX0183X
- Certificate No. (IECEX)
- IECEXKEM10.0090X
- Certificate no. (cULus)
- E337701
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther