Weidmuller

1176000000

ACT20M-AI-AO-S
1176000000
1176000000
1176000000
1176000000
1176000000
1176000000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€199.19
1
Payment methods:
A total of 17 Parts In-Stock from 13 Distributors

Additional Information

Part Number
1176000000

General Data

Accuracy
< 0.05 % of measuring range
Configuration
DIP switch
Galvanic isolation
3-way isolator
Power consumption, max.
1.2 W
Power consumption, typ.
0.84 W
Rail
TS 35
Step response time
≤ 7 ms
Temperature coefficient
≤ 0.01 % / °C
Voltage supply
24 V DC ± 30 %

Probability Of Failure

MTBF
231 Years

Approvals

Approvals
CE, CULUS, DETNORVER, DNV GL, EAC, FMEX, IECEXKEM, KEMAATEX
ROHS
Conform
UL File Number Search
E337701

Dimensions And Weights

Width
6.1 mm
Width (inches)
0.24 inch
Height
112.5 mm
Height (inches)
4.429 inch
Depth
114.3 mm
Depth (inches)
4.5 inch
Net weight
80 g

Connection Data

Type of connection
Screw connection
Tightening torque, min.
0.4 Nm
Tightening torque, max.
0.6 Nm
Clamping range, rated connection
2.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²
Wire connection cross section AWG, min.
AWG 30
Wire connection cross section AWG, max.
AWG 14

Rated Data Ul

UL certificate
E337701.pdf

Tender Specification Sheets

Long specification
Universal standard signal isolating amplifier1-channel signal isolating amplifier in 6.1 mm width with external power supply,for transmitting and isolating analogue DC current signals 0/4 to 20 mA and voltage signals 0/2 to 10 V // 0/1 to 5 V.Add-on housing for TS35 rail mountingDimensions: L/W/H 114.3/ 6.1/ 112.5 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20   Input                         0/4...20 mA                                      0/2...10 V or 0/1...10 VOutput                                             0/4...20 mA                                       0/2...10 V or 0/1...5 VLoad resistance             < 600 Ohm/ Strom/> 10 kOhm/ voltageTransmission error             < 0,05 % v. E. Limit frequency 100 HzAuxiliary power                                     24 VDC +/- 30 %Power loss approx. 0.8 WAmbient temperature range -25 °C...+70 °C Isolation                                 EN 61010-1, 3-way isolation up to 2.5 kV AC/DC of all circuits against each otherTest voltage                               2.5 kV input against output against auxiliary powerRated voltage                                          300 V AC/DC at overvoltage category II and pollution degree 2Approvals cULus, FM Div2, ATEX Zone2, DNV, GLType                                                             ACT20M-AI-AO-S
Short specification
Universal standard signal isolating amplifier1-channel signal isolating amplifier in 6.1 mm width with external power supply,for transmitting and isolating analogue DC current signals 0/4...20 mA and voltage signals0/2...10V // 0/1...5 V. I/O signals are configured with DIP switches.

Input

Number of inputs
1
Sensor
Voltage source, Current source, 2-wire transmitter (without own power supply)
Sensor supply
17…28 V DC (@ 20 mA)
Input voltage
configurable, 0(2)…10 V, 0(1)…5 V
Input resistance, voltage
>500 kΩ
Input current
configurable, 0...20 mA, 4…20mA
Voltage drop, current input
<1,5 V
Input resistance, current
70 Ω
Voltage drop
<1,5 V

Classifications

ETIM 6.0
EC002653
ETIM 7.0
EC002653
EClass 9.0
27-21-01-20
EClass 9.1
27-21-01-20
EClass 10.0
27-21-01-20

Output

Number of outputs
1
Output voltage, note
configurable, 0(2)...10 V, 0(1)...5 V
Output current
configurable, 0...20 mA, 4...20 mA
Cut-off frequency (-3 dB)
100 Hz
Load impedance voltage
≥ 10 kΩ
Load impedance current
≤ 600 Ω, @ max 23mA

Product Information

Product information
The configurable DC isolating amplifier ACT20M-AI-AO-S isolates and converts analogue standard signals. An analogue input signal is linearly converted into an analogue output signal and galvanically isolated. The input can also be operated as an active current loop (the loop current is supplied by the device). The power supply is galvanically isolated from the input and output (3-way isolation) by means of direct wiring or the Weidmüller rail bus. The configurable DC isolation amplifier ACT20M-AI-2AO-S offers the same functionality, but has 2 galvanically isolated outputs (4-way isolation).

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Data For Ex Applications (Atex)

Marking
II 3 G Ex nA IIC T4 Gc

Insulation Coordination

EMC standards
IEC 61326-1, NE 21
Galvanic isolation
3-way isolator
Insulation voltage
2.5 kVeff /1 min.
Pollution severity
2
Rated voltage
300 Veff
Surge voltage category
II

Temperatures

Humidity
40 °C / 93 % rel. humidity, no condensation
Operating temperature, max.
70 °C
Operating temperature, min.
-25 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-25 °C...70 °C
Ambient temperature
-25 °C...+70 °C
Storage temperature
-40 °C...85 °C

Ratings Iecex/Atex/Cul

Certificate No. (ATEX)
KEMA10ATEX0183X
Certificate No. (IECEX)
IECEXKEM10.0090X
Certificate no. (cULus)
E337701