Weidmuller

1176040000

ACT20M-CI-CO-OLP-S
1176040000
1176040000
1176040000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€153.03
1
Payment methods:
A total of 8 Parts In-Stock from 9 Distributors

Additional Information

Part Number
1176040000

General Data

Accuracy
< 0.05 % of measuring range
Configuration
none
Galvanic isolation
2-way isolator
Power consumption, max.
0.5 W
Rail
TS 35
Step response time
≤ 5 ms
Temperature coefficient
≤±0.02 µA x (Δ °C x V supply) @ Tamb > 25 °C
Voltage supply
Output loop powered

Approvals

Approvals
CULUS, DETNORVER, DNV GL, EAC, FMEX, IECEXKEM, KEMAATEX
ROHS
Conform
UL File Number Search
E337701

Dimensions And Weights

Width
6.1 mm
Width (inches)
0.24 inch
Height
112.5 mm
Height (inches)
4.429 inch
Depth
114.3 mm
Depth (inches)
4.5 inch
Net weight
80 g

Connection Data

Type of connection
Screw connection
Tightening torque, min.
0.4 Nm
Tightening torque, max.
0.6 Nm
Clamping range, rated connection
2.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²
Wire connection cross section AWG, min.
AWG 30
Wire connection cross section AWG, max.
AWG 14

Rated Data Ul

UL certificate
E337701.pdf

Tender Specification Sheets

Long specification
Standard signal isolating amplifier1-channel signal isolating amplifier in 6.1 mm width output-loop powered,for transmitting and isolating analogue DC current signals 0/4...20 mA.Add-on housing for TS35 rail mountingDimensions: L/W/H 114.3/ 6.1/ 112.5 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20   Input                         0/4...20 mAOutput                                             0/4...20 mALoad resistance             < 600 OhmTransmission error             < 0,1 % v. E. Limit frequency 100 HzAuxiliary power                                     0/4...20 mA output current loopPower loss approx. 0.9 WAmbient temperature range -25 °C...+70 °C Isolation                                EN 61010-1, 2-way isolation up to 2.5 kV AC/DCTest voltage                               2.5 kV input against output against auxiliary powerRated voltage                                          300 V AC/DC at overvoltage category II and pollution degree 2Approvals cULus, FM Div2, ATEX Zone2, DNV, GLType                                                             ACT20M-CI-CO-OLP-S
Short specification
Standard signal isolating amplifier1-channel signal isolating amplifier in 6.1 mm width with output current loop feed,for transmitting and isolating analogue DC current signals from 0/4 to 20 mA.

Input

Number of inputs
1
Sensor
2-wire transmitter (without own power supply)
Sensor supply
6…35 V (@ 20 mA)
Input current
4…20mA
Voltage drop, current input
Typical 2.5 V

Classifications

ETIM 6.0
EC002653
ETIM 7.0
EC002653
EClass 9.0
27-21-01-20
EClass 9.1
27-21-01-20
EClass 10.0
27-21-01-20

Output

Number of outputs
1
Output current
4...20 mA
Cut-off frequency (-3 dB)
100 Hz
Load impedance current
≤600 Ω (channel 1 + 2), @ max 23mA
Supply voltage (output)
6…35 V

Product Information

Product information
The passive isolator ACT20M-CI-CO-OLP-S isolates standard analogue current signals. An analogue input current signal is linearly converted into an analogue output current signal and is galvanically isolated. Power is supplied through the output measuring circuit (output loop-powered).

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Data For Ex Applications (Atex)

Marking
II 3 G Ex nA IIC T4 Gc

Insulation Coordination

EMC standards
IEC 61326-1, NE 21
Galvanic isolation
2-way isolator
Insulation voltage
2.5 kVeff /1 min.
Pollution severity
2
Rated voltage
300 Veff
Surge voltage category
II

Temperatures

Humidity
40 °C / 93 % rel. humidity, no condensation
Operating temperature, max.
70 °C
Operating temperature, min.
-25 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-25 °C...70 °C
Ambient temperature
-25 °C...+70 °C
Storage temperature
-40 °C...85 °C

Ratings Iecex/Atex/Cul

Certificate No. (ATEX)
KEMA10ATEX0183X
Certificate No. (IECEX)
IECEXKEM10.0090X
Certificate no. (cULus)
E337701