1
Payment methods:

Fibre Optic 100Basefx

Link budget multimode
12 dB
Max. TX multi-mode
-10 dBm
Min. TX multi-mode
-20 dBm
Receive sensitivity multi-mode
-32 dBm
System reserve multi-mode
-6 dBm
Typical distances multi-mode
5 km (50/125 μm, multi-mode cable), 4 km (62.5/125 μm multi-mode cable)
Wavelength multi-mode
1,300 nm

Approvals

Approvals
CE, CULUS, CULUSEX, DEMKOATEX, DNV GL, EAC
ROHS
Conform
UL File Number Search
E230683

Mtbf

MTBF
240,000 hrs
Database
Telcordia (Bellcore), GB

Dimensions And Weights

Width
94 mm
Width (inches)
3.701 inch
Height
135 mm
Height (inches)
5.315 inch
Depth
142.7 mm
Depth (inches)
5.618 inch
Net weight
1,630 g

Environmental Conditions

Humidity
5 to 95 % (non-condensing)
Operating temperature, max.
60 °C
Operating temperature, min.
0 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C

Guarantee

Time interval
5 years

Classifications

ETIM 6.0
EC000734
ETIM 7.0
EC000734
EClass 9.0
19-17-01-06
EClass 9.1
19-17-01-06
EClass 10.0
19-17-04-01

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Switch Characteristics

Bandwidth backplane
7.2 Gbps
IGMP-Groups
256
MAC table size
8 K
Max. number of available VLANs
64
Packet buffer size
2 Mbit
Priority queues
4
VLAN-ID max
4,094
VLAN-ID min
1

Technical Data

Housing main material
metal
Protection degree
IP30
Type of mounting
DIN rail, Panel (with optional mounting kit)

Emc Conformity And Approvals

EMC standards
EN 55032, EN 55024, CISPR 32, FCC Part 15 Subpart B Class A, IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV, IEC 61000-4-3 RS: 80 MHz to 1 Ghz: 10 V/m, IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0,5 kV, IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV, IEC 61000-4-6 CS: 10 V, IEC 61000-4-8
Explosive risk zone
UL/cUL, Class I, Division 2, Groups A, B, C and D, ATEX Zone 2 Ex nA nC IIC T4 Gc
Free fall
According to IEC 60068-2-32
Security
UL508, UL60950-1, CSA C22.2 No. 60950-1, EN60950-1
Ship use
DNV-GL
Shock
according to IEC 60068-2-27
Vibration
according to IEC 60068-2-6

Interfaces

Alarm contact
2 relay outputs with a current capacity of 1 A at 24 V DC
Console port interface
RS-232
Digital inputs
2 inputs with the same ground, isolated+13 To +30 V for logic "1"-30 To +3 V for logic "0"Max. input current: 8 mA
Fibre-optic ports
100BaseFX ports (SC connector), Multimode, 1000BaseSFP-Slot
LED indicator
PWR1, PWR2, FAULT, MSTR/HEAD, CPLR/TAIL, 10/100M (TP-Port), 100M (fibre-optic port)., 1000M (Gigabit-Port)
Note 1
When connecting a single-mode fiber transceiver over a short distance, we recommend using an attenuator to prevent the transceiver from being damaged by excessive optical power.
Number of ports
14 * RJ45 10/100BaseT(X), 2 * SC Multi-mode 100FX, 2 * combo-ports (10/100/1000BaseT(X) or 1000BaseSFP)
RJ45 ports
10/100BaseT(X) or 10/100/1000BaseT(X), auto negotiation

Power Supply

Connection type
2 removable 6-pin terminal blocks
Current consumption
0.61 A at 24 V
Overload current protection
Existing
Reverse polarity protection
Available
Supply voltage, max.
45 V DC
Supply voltage, min.
12 V DC
Voltage supply
24 V DC, 2 redundant inputs

Technology

Data switching
Store and Forward
Flow control
IEEE 802.3x flow control, Back pressure flow control
MIB
MIB-II, Ethernet-Like MIB, P-BRIDGE MIB, Q-BRIDGE MIB, Bridge MIB, RSTP MIB, RMON MIB Group 1, 2, 3, 9
Protocol
IGMPv1/v2, GMRP, GVRP, SNMPv1/v2c/v3, DHCP Server/Client, BootP, TFTP, SNTP, SMTP, RARP, RMON, HTTP, HTTPS, Telnet, Syslog, DHCP option 66/67/82, SSH, SNMP Inform, Modbus/TCP, LLDP, IEEE 1588 PTP, IPv6
Standard
IEEE 802.3 for 10BaseT, IEEE 802.3u for 100BaseT(X) and 100BaseFX, IEEE 802.3ab for 1000BaseT(X), IEEE 802.3z for 1000BaseX, IEEE 802.3x for flow control, IEEE 802.1D-2004 for the Spanning Tree protocol, IEEE 802.1w for Rapid STP, IEEE 802.1Q for VLAN tagging, IEEE 802.1p for Class of Service, IEEE 802.1X for authentication, IEEE 802.3ad for port trunk with LACP