Weidmuller

1315240000

UR20-8DO-P
1315240000
1315240000
1315240000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€67.05
1
Payment methods:
A total of 1,231 Parts In-Stock from 19 Distributors

Additional Information

Part Number
1315240000

General Data

Air humidity (operation)
10% to 95%, non-condensing as per DIN EN 61131-2
Air humidity (storage)
10% to 95%, non-condensing as per DIN EN 61131-2
Air humidity (transport)
10% to 95%, non-condensing as per DIN EN 61131-2
Air pressure (operation)
≥ 795 hPa (height ≤ 2000 m) as per DIN EN 61131-2
Air pressure (storage)
1013 hPa (height 0 m) to 700 hPa (height 3000 m) as per DIN EN 61131-2
Air pressure (transport)
1013 hPa (height 0 m) to 700 hPa (height 3000 m) as per DIN EN 61131-2
Pollution severity
2
Shock
15 g over 11 ms, half sinus wave, acc. to IEC 60068-2-27
Surge voltage category
II
Test voltage
500 V
UL 94 flammability rating
V-0
Vibration resistance
5 Hz ≤ f ≤ 8.4 Hz: 3.5-mm amplitude as per IEC 60068-2-6, 8.4 Hz ≤ f ≤ 150 Hz: 1 g acceleration as per IEC 60068-2-6

Approvals

Approvals
ABS, BURVER, CE, CULUS, CULUSEX, DEMKOATEX, DNV GL, EAC, IECEXULD, KOREANCERT, LLOYDSREG, RINA, WATEXIECEX
ROHS
Conform
UL File Number Search
E141197

Dimensions And Weights

Width
11.5 mm
Width (inches)
0.453 inch
Height
120 mm
Height (inches)
4.724 inch
Depth
76 mm
Depth (inches)
2.992 inch
Mounting dimension - height
128 mm
Net weight
87 g

Digital Outputs

Actuator connection
2-wire
Feedback-free
Yes
Individual channel diagnosis
No
Inductive load (DC13)
0.2 Hz
Lamp load (12 W)
1 kHz
Max. response time, high
100 μs
Max. response time, low
250 μs
Module diagnosis
Yes
Number of digital outputs
8
Output current per channel, max.
500 mA
Output current per module, max.
4,000 mA
Resistive load (min. 47 Ω)
1 kHz
Response time of the protective circuit (current limiting)
< 100μs
Short-circuit-proof
Yes (thermal cut-out)
Switch-off energy (inductive)
< 150 mJ / channel
Type
Lamp load, Ohmic, Inductive

Connection Data

Type of connection
PUSH IN
Wire connection cross section, finely stranded, max.
1.5 mm²
Wire connection cross-section, finely stranded, min.
0.14 mm²
Wire cross-section, finely stranded, max. (AWG)
AWG 16
Wire cross-section, finely stranded, min. (AWG)
AWG 26
Wire cross-section, solid, max.
1.5 mm²
Wire cross-section, solid, max. (AWG)
AWG 16
Wire cross-section, solid, min.
0.14 mm²
Wire cross-section, solid, min. (AWG)
AWG 26

Classifications

ETIM 6.0
EC001597
ETIM 7.0
EC001597
EClass 9.0
27-24-26-02
EClass 9.1
27-24-26-02
EClass 10.0
27-24-26-02

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

System Data

Diagnostic data
1 Bit
Field bus protocol
CANopen, DeviceNet, EtherCAT, EtherNet/IP, Modbus/TCP, PROFINET IRT, PROFIBUS DP-V1, POWERLINK
Galvanic isolation
500 V DC between the current paths
Interface
u-remote system bus
Module type
Digital output module
Possible connection
2-wire
Process data
1 Byte
Transmission speed of system bus, max.
48 Mbit

Temperatures

Operating temperature, max.
60 °C
Operating temperature, min.
-20 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-20 °C ... +60 °C
Storage temperature
-40 °C ... +85 °C

Power Supply

Current consumption from I
15 mA + load
Voltage supply
24 V DC +20 %/ -15 %, via the system bus