Weidmuller
1351270000
1 / 2
Description
Surge voltage arrester, Low voltage, 1000 V, without telecomm. contact, 40 kA- Part Number
- 1351270000
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
General Data
- Colour
- black, orange
- Design
- Installation housing; 3TE, Insta IP 20
- Optical function display
- green = OK; red = arrester is defective - replace
- Protection degree
- IP20
- Rail
- TS 35
- UL 94 flammability rating
- V-0
- Version
- without telecomm. contact
Approvals
- Approvals
- CE, EAC
- ROHS
- Conform
Insulation Coordination Acc. To En 50178
- Pollution severity
- 2
- Surge voltage category
- III
Dimensions And Weights
- Width
- 53.4 mm
- Width (inches)
- 2.102 inch
- Height
- 94 mm
- Height (inches)
- 3.701 inch
- Depth
- 69 mm
- Depth (inches)
- 2.717 inch
- Mounting dimension - height
- 75 mm
- Net weight
- 400 g
Connection Data
- Type of connection
- Screw connection
- Stripping length, rated connection
- 15 mm
- Tightening torque, min.
- 2 Nm
- Tightening torque, max.
- 3 Nm
- Clamping range, rated connection
- 16 mm²
- Clamping range, min.
- 2.5 mm²
- Clamping range, max.
- 35 mm²
- Wire cross-section, solid, min.
- 2.5 mm²
- Wire cross-section, solid, max.
- 16 mm²
- Wire connection cross-section, finely stranded, min.
- 2.5 mm²
- Wire connection cross section, finely stranded, max.
- 25 mm²
- Conductor cross-section, flexible, AEH (DIN 46228-1), min.
- 2.5 mm²
- Conductor cross-section, flexible, AEH (DIN 46228-1), max.
- 50 mm²
- Connection cross-section, stranded, min.
- 2.5 mm²
- Connection cross-section, stranded, max.
- 50 mm²
Tender Specification Sheets
- Long specification
- Multi-pole surge voltage arrestor according to the requirements of Class II acc. to IEC 50539-11. Consisting of V0 material, the arrestor serves as overvoltage protection in applications acc. to IEC 50539-12 in unearthed PV systems. The use of a high-performance varistor meets the inspection requirements for Class II surge protection systems on the basis of the standards. The arrestor is installed in the vicinity of the equipment that needs protection, in a commercially available installation/electrical distribution enclosure. With thermal separation device on the varistor. If protection is no longer available, the colour in the display window changes from green to red. Rated voltage: 1000 VDC In/max (8/20 µs): 20/40 kA, protection level < 4 kV, type: Weidmüller VPU II 3 PV 1000 V/40 kA, Order No. 1351270000 or equivalent
- Short specification
- Class II arrestor with In/Imax: 20/40 kA suitable for unearthed PV systems. Protection level < 4 kV. Type: Weidmüller VPU II 3 PV 1000 V/40 kA Order No. 1351270000 or equivalent
Classifications
- ETIM 6.0
- EC000941
- ETIM 7.0
- EC000941
- EClass 9.0
- 27-13-08-05
- EClass 9.1
- 27-13-08-05
- EClass 10.0
- 27-13-08-05
- UNSPSC
- 30-21-19-21
Photovoltaic Technical Data
- Conditions and requirements
- EN 50539-11
- Discharge current I
- 20 kA
- Discharge current, max. (8/20 µs)
- 40 kA
- Maximum continuous operating voltage UCPV mode +/-, -/PE, +/PE
- 1,000 V DC
- PV system voltage, max. U
- 1,000 V
- Protection level U
- ≤ 4.0 kV
- Requirements class
- Type II
- Short-circuit curent I
- 200 A
- Standards
- EN 50539-11
Temperatures
- Operating temperature, max.
- 70 °C
- Operating temperature, min.
- -40 °C
- Storage temperature, max.
- 80 °C
- Storage temperature, min.
- -40 °C
- Operating temperature
- -40 °C...70 °C
- Storage temperature
- -40 °C...80 °C
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther