- Discharge current I
- 20 kA
- Energy coordination (≤10 m)
- Type I, Type II, Type III
- Follow-on current extinguishing capability I
- Not available due for technical reasons
- Frequency range, max.
- 60 Hz
- Frequency range, min.
- 50 Hz
- Fuse
- 250 A gL (if back up fuse > 250 A)
- Leakage current at U
- 1 µA
- Lightning test current I
- 12.5 kA
- Lightning test current, I
- 50 kA
- Low voltage network
- TN-C-S, TN-S, TT, IT with N, IT without N
- Max. continuous voltage, Uc (AC)
- 280 V
- Max. continuous voltage, Uc (N-PE)
- 260 V
- Number of poles
- 4
- Protection level U
- ≤ 1.5 kV
- Rated voltage (AC)
- 230 V
- Requirements category acc. to IEC 61643-11
- Type I, Type II
- Requirements class, acc. to EN 61643-11
- T1, T2
- Response time
- ≤ 25 ns, ≤ 100 ns
- Short-circuit current rating I
- 25 kA
- Signalling contact
- 250 V 1A 1CO
- Standards
- IEC61643-11, EN61643-11
- Suitable for
- Count-in installation (leakage current free)
- Temporary surge voltage (over-voltage) - TOV
- 438 V
- Voltage type
- AC