- Combined pulse U
- 10 kV
- Discharge current I
- 20 kA
- Fuse
- 125 A gL > (if back up fuse > 125 A)
- Leakage current at U
- 1 µA
- Max. continuous voltage, Uc (AC)
- 280 V
- Number of poles
- 1
- Protection level U
- ≤ 1.8 kV
- Rated voltage (AC)
- 230 V
- Requirements category acc. to IEC 61643-11
- Type II, Type III
- Requirements class, acc. to EN 61643-11
- T2, T3
- Response time
- ≤ 100 ns
- Short-circuit current rating I
- 25 kA
- Standards
- IEC61643-11, EN61643-11
- Temporary surge voltage (over-voltage) - TOV
- 438 V
- Voltage type
- AC