Weidmuller
1352750000
VPU II 1 R LCF 280V/40KA
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
A total of 5 Parts In-Stock from 8 Distributors
Product Conditions:
General Data
- Colour
- black, orange
- Design
- Installation housing; 1TE, Insta IP 20
- Optical function display
- green = OK; red = arrester is defective - replace
- Protection degree
- IP20
- Rail
- TS 35
- UL 94 flammability rating
- V-0
- Version
- with remote contact
Approvals
- Approvals
- CE, EAC, OEVE
- ROHS
- Conform
Insulation Coordination Acc. To En 50178
- Pollution severity
- 2
- Surge voltage category
- III
Rated Data Iec / En
- Combined pulse U
- 10 kV
- Discharge current I
- 20 kA
- Energy coordination (≤10 m)
- Type II, Type III
- Follow-on current extinguishing capability I
- Not available due for technical reasons
- Frequency range, max.
- 60 Hz
- Frequency range, min.
- 50 Hz
- Fuse
- 125 A gL > (if back up fuse > 125 A)
- Leakage current at U
- 1 µA
- Low voltage network
- Single-phase
- Max. continuous voltage, Uc (AC)
- 280 V
- Number of poles
- 1
- Protection level U
- ≤ 1.8 kV
- Rated voltage (AC)
- 230 V
- Requirements category acc. to IEC 61643-11
- Type II, Type III
- Requirements class, acc. to EN 61643-11
- T2, T3
- Response time
- ≤ 100 ns
- Short-circuit current rating I
- 25 kA
- Signalling contact
- 250 V 1A 1CO
- Standards
- IEC61643-11, EN61643-11
- Temporary surge voltage (over-voltage) - TOV
- 438 V
- Voltage type
- AC
Dimensions And Weights
- Width
- 17.8 mm
- Width (inches)
- 0.701 inch
- Height
- 105 mm
- Height (inches)
- 4.134 inch
- Depth
- 69 mm
- Depth (inches)
- 2.717 inch
- Mounting dimension - height
- 75 mm
- Net weight
- 148 g
Connection Data
- Wire connection method
- Screw connection
- Type of connection
- Screw connection
- Stripping length, rated connection
- 15 mm
- Tightening torque, min.
- 2 Nm
- Tightening torque, max.
- 3 Nm
- Clamping range, rated connection
- 16 mm²
- Clamping range, min.
- 1.5 mm²
- Clamping range, max.
- 35 mm²
- Wire cross-section, solid, min.
- 1.5 mm²
- Wire cross-section, solid, max.
- 16 mm²
- Wire connection cross-section, finely stranded, min.
- 1.5 mm²
- Wire connection cross section, finely stranded, max.
- 25 mm²
- Conductor cross-section, flexible, AEH (DIN 46228-1), min.
- 1.5 mm²
- Conductor cross-section, flexible, AEH (DIN 46228-1), max.
- 50 mm²
- Connection cross-section, stranded, min.
- 1.5 mm²
- Connection cross-section, stranded, max.
- 50 mm²
Tender Specification Sheets
- Long specification
- Single-pole surge voltage arrestor according to the requirements of Class II/III acc. to IEC 61643-11, EN61643-11:2013. Consisting of V0 material, the arrestor serves as surge protection in applications acc. to IEC 61643-12. Surge protection is used in the TN, TT and IT mains system types in combination with several lightning protectors. The use of a high-performance varistor in combination with sparkover gaps satisfies the inspection requirements for Class II surge protection systems on the basis of the standards. The leakage current-free arrestor is installed in the vicinity of the power supply for the equipment that needs protection, in a commercially available installation/electrical distribution enclosure. The VPU II 1 R LCF 280 V/40 kA is earthed, in combination with three or four identical arrestors, between the outer conductors (L1, L2, L3 and / or the neutral conductor). Reference is also made here to the 3+1 circuit and the 3+0 / 4+0 circuits. With thermal separation device on the varistor. If protection is no longer available, the colour in the display window changes from green to red. The functional state is also displayed by a voltage-free signalling contact (changeover). Rated voltage: 230 VAC maximum discharge current (8/20 µs): 40 kA protection level < 1.8 kV combined pulse Uoc: 10 kV; 25 kA short-circuit strength with max. back-up fuse of 125 A gl telecommunication output: contact: 250 V/0.5 A 48 VDC/0.1 A Type: Weidmüller VPU II 1 R LCF 280 V/40 kA Order No. 1352750000 or equivalent
- Short specification
- Class II arrester with In/Imax: 20/40 kA suitable for 230/400 V mains systems. Protection level < 1.8 kV. With remote alert Type: Weidmüller VPU II 1 R LCF 280 V/12.5 kA Order no. 1352750000 or equivalent
Classifications
- ETIM 6.0
- EC000941
- ETIM 7.0
- EC000941
- EClass 9.0
- 27-13-08-05
- EClass 9.1
- 27-13-08-05
- EClass 10.0
- 27-13-08-05
- UNSPSC
- 30-21-19-21
Connection Data, Remote Alert
- Connection type
- PUSH IN
- Stripping length
- 8 mm
- Cross-section for connected wire, solid core, min.
- 0.14 mm²
- Cross-section for connected wire, solid core, max.
- 1.5 mm²
Temperatures
- Humidity
- 5 - 95% rel. humidity
- Operating temperature, max.
- 70 °C
- Operating temperature, min.
- -40 °C
- Storage temperature, max.
- 80 °C
- Storage temperature, min.
- -40 °C
- Operating temperature
- -40 °C...70 °C
- Storage temperature
- -40 °C...80 °C
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther