General Data

AC failure bridging time @ I
> 80 ms @ 230 V AC / > 20 ms @ 115 V AC
Degree of efficiency
87 %
Earth leakage current, max.
3.5 mA
Housing version
Metal, corrosion resistant
Indication
Green LED (Uoutput > 21.6 V DC), Yellow LED (loutput > 90 % IRated typ. ), red LED (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
MTBF
> 500,000 h in accordance with IEC 61709 (SN29500)
Max. perm. air humidity (operational)
5 %…95 % RH
Mounting position, installation notice
on terminal rail TS 35
Operating temperature
-25 °C...70 °C
Power factor (approx.)
> 0.5…230 V AC / > 0.53…115 V AC
Power loss, idling
4 W
Power loss, nominal load
15 W
Protection against over-heating
Yes
Protection against reverse voltages from the load
30…35 V DC
Protection degree
IP20
Short-circuit protection
Yes

Signalling

Contact load (NO contact)
max. 30 V DC / 1 A
Floating contact
Yes
Relay on/off
Output voltage >21.6 V DC/ <20.4 V DC, overload

Connection Data (Input)

Conductor cross-section, AWG/kcmil , max.
12
Conductor cross-section, AWG/kcmil , min.
26
Conductor cross-section, flexible , min.
0.5 mm²
Conductor cross-section, rigid , max.
6 mm²
Conductor cross-section, rigid , min.
0.5 mm²
Connection system
Screw connection
Number of terminals
3 for L/N/PE
Tightening torque, max.
0.6 Nm
Tightening torque, min.
0.5 Nm
Wire connection cross section, flexible (input), max.
2.5 mm²

Approvals

Approvals
CE, CULUS, EAC, TUEV
ROHS
Conform
UL File Number Search
E258476

Dimensions And Weights

Width
40 mm
Width (inches)
1.575 inch
Height
125 mm
Height (inches)
4.921 inch
Depth
100 mm
Depth (inches)
3.937 inch
Net weight
675 g

Electrical Safety (Applied Standards)

Electrical machine equipment
Acc. to EN60204
For use with electronic equipment
Acc. to EN50178 / VDE0160
Protection against dangerous shock currents
Acc. to VDE0106-101
Protective separation / protection against electrical shock
VDE0100-410 / acc. to DIN57100-410
Safety extra-low voltage
SELV according to EN 60950, PELV according to EN 60204
Safety transformers for switch-mode power supplies
According to EN 61558-2-16

Emc / Shock / Vibration

Limiting of mains voltage harmonic currents
According to EN 61000-3-2
Noise emission in accordance with EN55032
Class B
Vibration resistance IEC 60068-2-6
1 g according to EN 50178
Interference immunity test acc. to
EN 61000-4-2 (ESD), EN 61000-4-3 (RS), EN 61000-4-4 (burst), EN 61000-4-5 (surge), EN 61000-4-6 (conducted), EN61000-4-8 (Fields), EN61000-4-11 (Dips)
Shock resistance IEC 60068-2-27
15 g In all directions

Input

AC current consumption
1,26 A @ 230 V AC / 2,24 A @ 110 V AC
AC input voltage range
85...264 V AC (derating at 100 V AC)
Connection system
Screw connection
DC current consumption
0,39 A @ 370 V DC / 1,16 A @ 120 V DC
DC input voltage range
80...370 V DC (Derating @ 120 V DC)
Frequency range AC
47...63 Hz
Input frequency
47...63 Hz
Input fuse (internal)
Yes
Inrush current
max. 40 A
Rated input voltage
100...240 V AC (wide-range input)
Recommended back-up fuse
4 A / DI, safety fuse6 A, Char. B, circuit breaker3...5 A, Char. C, circuit breaker
Surge protection
Varistor

Classifications

ETIM 6.0
EC002540
ETIM 7.0
EC002540
EClass 9.0
27-04-07-01
EClass 9.1
27-04-07-01
EClass 10.0
27-04-07-01

Output

Capacitive load
unrestricted
Connection system
Screw connection
Continous output current @ U
5 A @ 55 °C, 3,75 A @ 70 °C
Nominal output current for U
5 A at 55 °C
Output power
120 W
Output voltage
22...28 V (adjustable via potentiometer)
Overload protection
Yes
Parallel connection option
yes, max. 5
Protection against inverse voltage
Yes
Ramp-up time
≤ 100 ms
Rated output voltage
24 V DC ± 1 %
Residual ripple, breaking spikes
< 50 mVPP @ 24 V DC, IN

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

Insulation voltage input / earth
2 kV
Insulation voltage output / earth
0.5 kV
Insulation voltage, input/output
3 kV
Pollution severity
2
Protection class
I, with PE connection

Connection Data (Output)

Conductor cross-section, AWG/kcmil , max.
12
Conductor cross-section, AWG/kcmil , min.
26
Conductor cross-section, flexible , max.
2.5 mm²
Conductor cross-section, flexible , min.
0.5 mm²
Conductor cross-section, rigid , max.
6 mm²
Conductor cross-section, rigid , min.
0.5 mm²
Connection system
Screw connection
Number of terminals
6 (++,--,13,14)
Tightening torque, max.
0.6 Nm
Tightening torque, min.
0.5 Nm

Temperatures

Operating temperature, max.
70 °C
Operating temperature, min.
-25 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-25 °C...70 °C
Storage temperature
-40 °C...85 °C

Ratings Iecex/Atex/Cul

Certificate no. (cULus)
E258476