Weidmuller

1933550000

BLZ DN 5.08/05/180F AU GY BX PRT
1933550000
1933550000
1933550000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price

Additional Information

Part Number
1933550000

Rated Data Acc. To Ul 1059

Institute (cURus)
cURus
Certificate No. (cURus)
E60693
Rated voltage (Use group B / UL 1059)
300 V
Rated voltage (Use group D / UL 1059)
300 V
Rated current (Use group B / UL 1059)
15 A
Rated current (Use group D / UL 1059)
10 A
Wire cross-section, AWG, min.
AWG 22
Wire cross-section, AWG, max.
AWG 12
Reference to approval values
Specifications are maximum values, details - see approval certificate.

Approvals

Approvals
cURus, EAC
ROHS
Conform
UL File Number Search
E60693

Dimensions And Weights

Width
35.2 mm
Width (inches)
1.386 inch
Height
15.25 mm
Height (inches)
0.6 inch
Depth
21.2 mm
Depth (inches)
0.835 inch
Net weight
10.12 g

Rated Data Acc. To Iec

Tested acc. to standard
IEC 60664-1, IEC 61984
Rated current, min. number of poles (Tu=20°C)
15 A
Rated current, max. number of poles (Tu=20°C)
12 A
Rated current, min. number of poles (Tu=40°C)
12 A
Rated current, max. number of poles (Tu=40°C)
10 A
Rated voltage for surge voltage class / pollution degree II/2
400 V
Rated voltage for surge voltage class / pollution degree III/2
320 V
Rated voltage for surge voltage class / pollution degree III/3
250 V
Rated impulse voltage for surge voltage class/ pollution degree II/2
4 kV
Rated impulse voltage for surge voltage class/ pollution degree III/2
4 kV
Rated impulse voltage for surge voltage class/ contamination degree III/3
4 kV
Short-time withstand current resistance
3 x 1s with 120 A

Material Data

Insulating material
PBT
Colour
Pebble grey
Colour chart (similar)
RAL 7032
Insulation strength
≥ 108 Ω
UL 94 flammability rating
V-0
GWFI
960 °C
Contact material
Copper alloy
Contact surface
Gold-plated
Layer structure of plug contact
2-3 µm Ni / 1.5- µm Au
Storage temperature, min.
-25 °C
Storage temperature, max.
55 °C
Max. relative humidity during storage
80 %
Operating temperature, min.
-50 °C
Operating temperature, max.
100 °C
Temperature range, installation, min.
-25 °C
Temperature range, installation, max.
100 °C

Classifications

ETIM 6.0
EC002638
ETIM 7.0
EC002638
EClass 9.0
27-44-03-09
EClass 9.1
27-44-03-09
EClass 10.0
27-44-03-09
UNSPSC
30-21-18-10

System Parameters

Product family
OMNIMATE Signal - series BL/SL 5.08
Type of connection
Field connection
Wire connection method
Clamping yoke connection
Pitch in mm (P)
5.08 mm
Pitch in inches (P)
0.2 inch
Conductor outlet direction
180°
Number of poles
5
L1 in mm
20.32 mm
L1 in inches
0.8 inch
Number of rows
1
Pin series quantity
1
Rated cross-section
2.5 mm²
Touch-safe protection acc. to DIN VDE 57 106
Safe from finger touch
Volume resistance
5.00 mΩ
Can be coded
Yes
Stripping length
7 mm
Tightening torque for screw flange, min.
0.15 Nm
Tightening torque for screw flange, max.
0.2 Nm
Tightening torque, min.
0.4 Nm
Tightening torque, max.
0.5 Nm
Clamping screw
M 2.5
Screwdriver blade
0.6 x 3.5
Screwdriver blade standard
DIN 5264
Plugging cycles
25
Plugging force/pole, max.
8.5 N
Pulling force/pole, max.
6.5 N

Packing

Packaging
Box
VPE length
40 mm
VPE width
100 mm
VPE height
220 mm

Notes

Notes
Additional colours on request Rated current related to rated cross-section & min. No. of poles. Wire end ferrule without plastic collar to DIN 46228/1 Wire end ferrule with plastic collar to DIN 46228/4 P on drawing = pitch Rated data refer only to the component itself. Clearance and creepage distances to other components are to be designed in accordance with the relevant application standards.
IPC conformity
Conformity: The products are developed, manufactured and delivered according international recognized standards and norms and comply with the assured properties in the data sheet resp. fulfill decorative properties in accordance with IPC-A-610 "Class 2". Further claims on the products can be evaluated on request.

Conductors Suitable For Connection

Clamping range, min.
0.13 mm²
Clamping range, max.
3.31 mm²
Wire connection cross section AWG, min.
AWG 26
Wire connection cross section AWG, max.
AWG 12
Solid, min. H05(07) V-U
0.2 mm²
Solid, max. H05(07) V-U
2.5 mm²
Flexible, min. H05(07) V-K
0.2 mm²
Flexible, max. H05(07) V-K
2.5 mm²
W. plastic collar ferrule, DIN 46228 pt 4, min.
0.2 mm²
W. plastic collar ferrule, DIN 46228 pt 4, max.
2.5 mm²
W. wire end ferrule, DIN 46228 pt 1, min.
0.2 mm²
W. wire end ferrule, DIN 46228 pt 1, max.
2.5 mm²
Plug gauge in accordance with EN 60999 a x b; ø
2.8 mm x 2.0 mm; 2.4 mm
Reference text
The outside diameter of the plastic collar should not be larger than the pitch (P).
Max. clamping range
3.31 mm²

Rated Data Acc. To Csa

Rated voltage (Use group B / CSA)
300 V
Rated voltage (Use group D / CSA)
300 V
Rated current (Use group B / CSA)
15 A
Rated current (Use group D / CSA)
10 A
Wire cross-section, AWG, min.
AWG 26
Wire cross-section, AWG, max.
AWG 12