Weidmuller

2636930000

VPU AC I 1+1 300/12.5 LCF
2636930000
2636930000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 2 Parts In-Stock from 8 Distributors

General Data

Altitude
≤ 4000 m
Colour
orange, black, blue
Design
Installation housing; 2TE, Insta IP 20
Optical function display
green = OK; red = arrester is defective - replace
Protection degree
IP20 in installed state
Rail
TS 35
Segment
Power distribution
Suitable for
Count-in installation (leakage current free)
UL 94 flammability rating
V-0
Version
Surge protection

Approvals

Approvals
CE, cURus, EAC, VDE
ROHS
Conform
UL File Number Search
E354261

Insulation Coordination Acc. To En 50178

Pollution severity
2
Surge voltage category
IV, III, II, I

Rated Data Iec / En

Discharge current I
20 kA
Energy coordination (≤10 m)
Type I, Type II, Type III
Follow-on current extinguishing capability I
Not available due for technical reasons
Frequency range, max.
60 Hz
Frequency range, min.
50 Hz
Fuse
250 gG @50 kA Isccr, 315 gG @25 kA Isccr
Leakage current at U
1 µA
Lightning test current I
12.5 kA
Lightning test current, I
50 kA
Low voltage network
Single-phase, TN-C, TN-C-S, TN-S
Max. continuous voltage, Uc (AC)
300 V
Max. continuous voltage, Uc (N-PE)
305 V
Number of poles
2
Protection level U
≤ 1.5 kV
Rated voltage (AC)
230 V
Requirements category acc. to IEC 61643-11
Type I, Type II
Requirements class, acc. to EN 61643-11
T1, T2
Response time
≤ 25 ns, ≤ 100 ns
Short-circuit current rating I
50 kA
Signalling contact
No
Standards
IEC61643-11, EN61643-11
Suitable for
Count-in installation (leakage current free)
Temporary surge voltage (over-voltage) - TOV
442 V
Voltage type
AC

Dimensions And Weights

Width
36 mm
Width (inches)
1.417 inch
Height
90 mm
Height (inches)
3.543 inch
Depth
93 mm
Depth (inches)
3.661 inch
Net weight
309 g

Connection Data

Wire connection method
Screw connection
Type of connection
Screw connection
Stripping length, rated connection
15 mm
Tightening torque, min.
2 Nm
Tightening torque, max.
4.5 Nm
Clamping range, rated connection
16 mm²
Clamping range, min.
4 mm²
Clamping range, max.
35 mm²
Wire cross-section, solid, min.
2.5 mm²
Wire cross-section, solid, max.
35 mm²
Wire connection cross-section, finely stranded, min.
2.5 mm²
Wire connection cross section, finely stranded, max.
35 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min.
2.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max.
35 mm²
Connection cross-section, stranded, min.
2.5 mm²
Connection cross-section, stranded, max.
35 mm²

Rated Data Ul

Voltage type
AC
Certificate No. (cURus)
E354261
Rated Voltage U
240 V
MCOV (L/N-PE)
300 Vac
MCOV (N-PE)
305 V
I
20 kA
Category
SPD TYPE 4CA

Classifications

ETIM 6.0
EC000941
ETIM 7.0
EC000941
EClass 9.0
27-13-08-05
EClass 9.1
27-13-08-05
EClass 10.0
27-13-08-05

Temperatures

Humidity
5 - 95% rel. humidity
Operating temperature, max.
70 °C
Operating temperature, min.
-40 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-40 °C...70 °C
Storage temperature
-40 °C...85 °C