Weidmuller

7760054115

ACT20P-CI-2CO-S
7760054115
7760054115
7760054115
7760054115
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€183.02
1
Payment methods:
A total of 24 Parts In-Stock from 15 Distributors
Offer with manufacturer lead time
Ships in:On Request
Best price:
€131.76

Additional Information

Part Number
7760054115

General Data

Accuracy
< 0.1 % of end value
Configuration
none
Current consumption
≤60 mA (24V power supply, 20mA output)
Galvanic isolation
3-way isolator, between input ⁄ output ⁄ supply
Rail
TS 35
Step response time
≤ 0,5 ms
Temperature coefficient
80 ppm/K
Voltage supply
20…30 V DC

Approvals

Approvals
CE, CULUS, EAC
ROHS
Conform
UL File Number Search
E366074

Dimensions And Weights

Width
12.5 mm
Width (inches)
0.492 inch
Height
117.2 mm
Height (inches)
4.614 inch
Depth
113.7 mm
Depth (inches)
4.476 inch
Weight
157 g
Net weight
157 g

Connection Data

Type of connection
Screw connection
Tightening torque, min.
0.4 Nm
Tightening torque, max.
0.6 Nm
Clamping range, rated connection
2.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²
Wire connection cross section AWG, min.
AWG 26
Wire connection cross section AWG, max.
AWG 12

Input

Number of inputs
1
Sensor supply
> 17 V DC at 20 mA, max 30 V @ open circuit, max 50 mA @ short-circuit
Input signal
2-/3-wire transmitter, HART signal® bidirectional
Input current
0...20 mA, 4…20mA
Voltage drop
ca. 3.8 V @ RLoad = 0 Ω; ca. 15 V @ RLoad = 600 Ω; (Iinput = 20 mA)

Classifications

ETIM 6.0
EC002653
ETIM 7.0
EC002653
EClass 9.0
27-21-01-20
EClass 9.1
27-21-01-20
EClass 10.0
27-21-01-20

Output

Number of outputs
2
Output current
0...20 mA, 4...20 mA, HART® digital signal
Load impedance current
< 300 Ω

Product Information

Product information
The non-adjustable DC isolating amplifier ACT20P-CI-2CO isolates analogue standard current signals from a power source or from a 2- or 3-wire sensor. An analogue input current signal is converted linearly and doubled to provide two galvanically isolated output current signals. The power supply is galvanically isolated from the input and output (4-way isolation). Properties HART-compatible for 0.5 - 2.5 kHz The active or passive mA signal inputs are fully galvanically isolated. Operating status display on a front panel LED Galvanic 4-way isolation between input, output and supply.

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

EMC standards
EN 61010-1:2011, UL 61010-1, EN 61326-1
Galvanic isolation
3-way isolator, between input ⁄ output ⁄ supply
Impulse withstand voltage
4 kV (1.2/50 µs)
Insulation voltage
2 kV inputs / outputs / power supply
Insulation voltage input or output/supply
2 kV inputs / outputs / power supply
Pollution severity
2
Surge voltage category
III

Temperatures

Humidity
5...95 %, no condensation
Operating temperature, max.
60 °C
Operating temperature, min.
-20 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-20 °C...60 °C
Storage temperature
-40 °C...85 °C

Ratings Iecex/Atex/Cul

Certificate no. (cULus)
E366074