Weidmuller
7940014374
PTX800A 4-20mA/RO/AO
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price
Additional Information
- Part Number
- 7940014374
General Data
- Data backup
- ≥ 100 years
- Humidity
- 10…90 %, no condensation
- Input/Output
- With analogue/alarm output
- Linearity
- < 0.05 %
- Long-term drift
- 0.1 % / 10.000 h
- Power consumption
- 6 W @ 24 V DC
- Switching current
- 3 A @ 240 V AC, 5 A @ 24 V DC / 110 V AC (resistive load)
- Type of connection
- Screw connection
- Voltage supply
- 24 V DC ± 10 %
- Weight
- 461 g
Reset Input
- Function (reset input)
- Complete reset (display / alarm)
- Min. pulse duration (reset input)
- 250 ms
- Type (reset input)
- NO contact
Approvals
- Approvals
- CE, CULUS
- ROHS
- Conform
- UL File Number Search
- E256486
Display
- Decimal point
- Independently adjustable for partial or total display
- Display value
- Percentage or real value display
- Partial display
- Display range of 0...50.000 (5-digit)
- Time range (partial display)
- per sec, min, hour (and day for PTX800A)
- Total display
- Display from 0...99,999,999 (8 digits)
- Total display, display range
- 0,001; 0,01; 0,1; 1; 10; 100; 1000
- Type
- 8-digit, red LED, 7.2 mm14 adjustable brightness levels
Dimensions And Weights
- Length
- 137 mm
- Length (inches)
- 5.394 inch
- Width
- 96.6 mm
- Width (inches)
- 3.803 inch
- Height
- 48.8 mm
- Height (inches)
- 1.921 inch
- Weight
- 461 g
- Net weight
- 461 g
Connection Data
- Type of connection
- Screw connection
- Clamping range, rated connection
- 1.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, max.
- 2.5 mm²
Analogue Output
- Load resistance current (analogue output)
- ≤ 900 Ω
- Load resistance voltage (analogue output)
- ≥ 1 kΩ
- Residual ripple (analogue output)
- ≤ 20 mVss
- Resolution (analogue output)
- 1.6 µA or 0.8 mV / bit
- Type (analogue output)
- Current of voltage output, configured with jumper
Alarm
- Switching current
- 3 A @ 240 V AC, 5 A @ 24 V DC / 110 V AC (resistive load)
- Type
- 2 relay contacts (CO)
Pulse Output
- Cut-off time (pulse output)
- min. 32 ms
- Display value (pulse output)
- 1 pulse per signal jump on the total display
- Pulse duration
- 32 ms
- Pulse rate, max. (pulse output)
- 15 / s
- Type (pulse output)
- Transistor output
Input
- Input resistance
- 22 Ω (current input); 1 MΩ (voltage input)
- Input signal
- -24...+24 mA / -11...+11 V
- Resolution
- 0.6 µ, A / 0.3 mV
- Sensor supply
- 24 V DC (up to 25 mA)
- Type
- Conversion of linear/quadratic input signals into analogue signals
Classifications
- ETIM 6.0
- EC000677
- ETIM 7.0
- EC000677
- EClass 9.0
- 27-14-31-10
- EClass 9.1
- 27-21-03-01
- EClass 10.0
- 27-14-31-10
- UNSPSC
- 30-21-18-01
Output
- Residual ripple (analogue output)
- ≤ 20 mVss
- Type
- RO/AO version with 1 analogue output and 2 alarm outputs
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Insulation Coordination
- EMC standards
- DIN EN 61326
- Impulse withstand voltage
- 4 kV (1.2/50 µs)
Temperatures
- Humidity
- 10…90 %, no condensation
- Operating temperature, max.
- 60 °C
- Operating temperature, min.
- 0 °C
- Storage temperature, max.
- 70 °C
- Storage temperature, min.
- -25 °C
- Operating temperature
- 0 °C...60 °C
- Storage temperature
- -25 °C...70 °C
Ratings Iecex/Atex/Cul
- Certificate no. (cULus)
- E256486
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther