Description

Signal converter/insulator, Configurable for 4 ranges , 0...20 mA or 0...11 V
Part Number
7940015595
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

General Data

Cut-off frequency (-3 dB)
5 Hz
Data backup
≥ 100 years (without power supply)
Humidity
0...90 % (no condensation)
Input/Output
without analogue/alarm output
Linearity
< 0.05 %
Long-term drift
0.1 % / 10.000 h
Power consumption
6 W @ 24 V DC
Step response time
< 220 ms (10...90 %)
Switching current
Channel 3/4: 3 A @ 240 V AC / 24 V DC (resistive load)
Transmit function
direct or inverted
Type of connection
Screw connection
Voltage supply
24 V DC ± 10 %
Weight
383 g

Approvals

Approvals
CE, CULUS
ROHS
Conform
UL File Number Search
E205105

Display

Display range
-9999...9999
Display value
Percentage or real value display
Scaling
Variable
Type
4-digit, red LED, 14.2 mmVoltage input/ current input

Dimensions And Weights

Length
137 mm
Length (inches)
5.394 inch
Width
96.6 mm
Width (inches)
3.803 inch
Height
48.8 mm
Height (inches)
1.921 inch
Weight
383 g
Net weight
383 g

Connection Data

Type of connection
Screw connection
Clamping range, rated connection
1.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²

Alarm

Number of channels, alarm
4
Rated switching current
200 mA
Rated switching voltage
50 V DC
Switching current
Channel 3/4: 3 A @ 240 V AC / 24 V DC (resistive load)
Type
Channel 1/2: transistor outputchannel 3/4: relay contact (CO)

Input

Attenuation factor
0...99, programmable digital filter
Input signal
Configurable for 4 ranges
Input voltage
50 mV to 250 V AC / 3 to 250 V DC
Sensor supply
12 V DC to 25 mA
Type
Adjustable frequencies

Classifications

ETIM 6.0
EC000677
ETIM 7.0
EC000677
EClass 9.0
27-14-31-10
EClass 9.1
27-21-03-01
EClass 10.0
27-14-31-10
UNSPSC
30-21-18-01

Output

Last resistor, max.
≤ 850 Ω (current); ≥ 1MΩ (voltage)
Output signal
0...20 mA or 0...11 V
Scaling
Variable
Transmit function
direct or inverted
Type
RO/AO version with 1 analogue output and 2 alarm outputs

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Functions

Step response time
< 220 ms (10...90 %)

Insulation Coordination

EMC standards
DIN EN 61326
Impulse withstand voltage
4 kV (1.2/50 µs)

Temperatures

Humidity
0...90 % (no condensation)
Operating temperature, max.
60 °C
Operating temperature, min.
0 °C
Storage temperature, max.
70 °C
Storage temperature, min.
-25 °C
Operating temperature
0 °C...60 °C
Storage temperature
-25 °C...70 °C

Ratings Iecex/Atex/Cul

Certificate no. (cULus)
E205105