Weidmuller

8516560000

WAS2 CMR 1/5/10A AC...
8516560000
8516560000
Part Number
8516560000
Free Shipping!
1
Payment methods:
Best offer from:
ITTrusted Automa.Net Supplier
Availability:
0 pcs.
On Request
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original packaging, factory sealed.

Additional Information

Part Number
8516560000

General Data

Configuration
DIP switch, Potentiometer
Current consumption
8.3 mA (relay not triggered)/ 24 mA (relay triggered)
Current-carrying capacity of cross-connect.
≤ 2 A
Galvanic isolation
3-way isolator
Input/Output
1/ 5/ 10 A AC / relay
Power consumption
≤ 0.8 W
Rail
TS 35
Step response time
typ. 700 ms
Temperature coefficient
≤ 800 ppm/K
Voltage supply
24 V DC ± 10 %

Probability Of Failure

MTTF
787 Years

Approvals

Approvals
CE, CULUS, EAC
ROHS
Conform
UL File Number Search
E141197

Dimensions And Weights

Length
92.4 mm
Length (inches)
3.638 inch
Width
22.5 mm
Width (inches)
0.886 inch
Depth
112.4 mm
Depth (inches)
4.425 inch
Weight
150 g
Net weight
116.9 g

Output (Digital)

Hysteresis
5 % or 10 % of threshold value
Max. switching voltage, DC
60 V
Max. switching voltage, AC
250 V
Continuous current
3 A

Connection Data

Wire connection method
Screw connection
Type of connection
Screw connection
Clamping range, rated connection
2.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²

Tender Specification Sheets

Long specification
Limit-value monitoring component   for AC currents up to 10A with relay outputand electrical isolationlimit-value monitoring component in 22.5 mm width for recording 50/ 60 Hz ACcurrents 0...1 A / 0...5 A / 0...10 A. A relay contact (CO)with a switching capacity of 750 VA is available on the output side.Input range can be selected using DIP switches. Switching threshold is adjustable between 10...90 % using the potentiometer on the front side. The 24 VDC power is supplied over the input circuit.The input and outputs are designed with 4 kV of electrical isolation.Add-on housing for TS35 rail mountingDimensions: L/W/H 92.4/ 22.5/ 112.4 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20   Input                         0...1 A / 0...5 A / 0...10 A AC switchable                                      50 / 60 Hz // transformer basedVoltage of measuring circuit 250 V ACOutput                                             Relay / COSwitching current 3 ASwitching voltage 6... 250 V AC / 6...60 V DCSwitching threshold 10...90 % via potentiometerHysteresis                     5 % or 10 %  . Temperature coefficient   < 800 ppm KStep response time typ. 700 msAuxiliary power                                     24 VDC +/- 10 % via output circuitAmbient temperature range 0 °C...+50 °C Secure isolation                   EN 50178, 2-way isolation up to 4 kVTest voltage                               4 kVeff / 5s input against outputRated voltage                                          300 V AC/DC at overvoltage category III and pollution degree 2Approvals cULusType                                                             WAS2 CMR 1/5/10A ac
Short specification
Limit-value monitoring component  for AC currents up to 10A with relay output and electrical isolationlimit-value monitoring component in 22.5 mm width for recording 50/ 60 Hz AC currents 0...1 A / 0...5 A / 0...10 A.  A relay contact (CO) with a switching capacity of 750 VA is available on the output side. Input range can be selected using DIP switches. Switching threshold adjustable between 10...90 % using the front-side potentiometer. The 24 VDC power is supplied over the input circuit. The input and output have 4 kV of electrical isolation.

Input

Number of inputs
1
Input current
0...1 A AC/ 0...5 A AC/ 0...10 A AC
Input frequency
50...60Hz

Classifications

ETIM 6.0
EC002653
ETIM 7.0
EC002653
EClass 9.0
27-21-01-20
EClass 9.1
27-21-01-20
EClass 10.0
27-21-01-20
UNSPSC
30-21-18-01

Output

Number of outputs
1
Contact assembly
1 CO contact
Switching thresholds
Adjustable 10...100% with front potentiometer
Status indicator
Green LED

Product Information

Product information
This product will soon be replaced by a new product.Please do not use with new systems. Please contact our technical support.

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

Clearance & creepage distances
≥ 3 mm
EMC standards
EN 55011, EN 61000-6
Galvanic isolation
3-way isolator
Impulse withstand voltage
4 kV
Insulation voltage
4 kVeff / 5 s
Pollution severity
2
Rated voltage
300 V
Surge voltage category
III

Temperatures

Operating temperature, max.
50 °C
Operating temperature, min.
0 °C
Storage temperature, max.
70 °C
Storage temperature, min.
-20 °C
Operating temperature
0 °C...50 °C
Storage temperature
-20 °C...70 °C

Ratings Iecex/Atex/Cul

Certificate no. (cULus)
E141197