Weidmuller

8581230000

WAZ2 VMA V AC
8581230000
8581230000
8581230000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 1 Part In-Stock from 5 Distributors
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price

Additional Information

Part Number
8581230000

General Data

Accuracy
1,3 % (40...60 Hz) typ. 1 %; 2 % (70...400 Hz) typ. 1,5 %
Configuration
DIP switch
Current consumption
40...30...24 mA @ IOUT =20 mA
Current-carrying capacity of cross-connect.
≤ 2 A
Galvanic isolation
3-way isolator
Input/Output
configurable
Rail
TS 35
Step response time
< 300 ms
Temperature coefficient
≤ 250 ppm/K
Voltage supply
24 V DC ± 25 %

Probability Of Failure

MTTF
371 Years

Approvals

Approvals
CE, CULUS, EAC
ROHS
Conform
UL File Number Search
E141197

Dimensions And Weights

Length
92.4 mm
Length (inches)
3.638 inch
Width
22.5 mm
Width (inches)
0.886 inch
Depth
112.4 mm
Depth (inches)
4.425 inch
Net weight
179 g

Connection Data

Type of connection
Tension-clamp connection
Clamping range, rated connection
1.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²

Tender Specification Sheets

Long specification
Monitoring component for AC voltages up to 450 V with standard signal output and electrical isolationVoltage monitoring component in 22.5 mm width for recording 50/ 60 Hz AC voltages 0...30 V / 0...70 V / 0...130 V / 0...250 V / 0...450 V. Standardised analogue current/voltage signals are available on the output side. The component has 4 kV of complete 3-way isolation and is supplied externally with 24 VDC. Add-on housing for TS35 rail mounting Dimensions: L/W/H 92.4/ 22.5/ 112.4 mm Tension-clamp connection / Nominal cross-section 1.5 mm2Protection degree: IP 20   Input                         0...30 V / 0...70 V / 0...130 V / 0...250 V / 0...450 V AC                                       40...400 Hz sinus Voltage of measuring circuit max 475 V AC Output                                             0(4)...20 mA / 0...10 V Load resistance            < 600 Ohm Strom >1 kOhm / voltageTransmission error           < 1,3 % v. E.  Temperature coefficient 250 ppm / K Step response time        < 300 msAuxiliary power                                     24 VDC +/- 25 % Ambient temperature range 0 °C...+50 °C Secure isolation                   EN 50178, 3-way isolation up to 4 kVTest voltage                               4 kV / 5 s Input / Output / supplyRated voltage                                          300 V AC/DC at overvoltage category III and pollution degree 2 Approvals cULus Type                                                             WAZ2 VMA V ac
Short specification
Monitoring component for AC voltages up to 450 V with standard signal outputand electrical isolationVoltage monitoring component in 22.5 mm width for recording 50/ 60 Hz ACvoltages 0...30 V / 0...70 V / 0...130 V / 0...250 V / 0...450 V. Standardised analogue current/voltage signals are available on the output side.The component has 4 kV of complete 3-way isolation and is supplied externally with 24 VDC.

Input

Number of inputs
1
Input resistance, voltage
30 kΩ / 70 kΩ / 130 kΩ / 250 kΩ / 450 kΩ
Input measurement range
0…30 V AC, 0…70 V AC, 0…130 V AC, 0…250 V AC, 0…450 V AC
Input frequency
40...400 Hz sinus

Classifications

ETIM 6.0
EC002653
ETIM 7.0
EC002653
EClass 9.0
27-21-01-20
EClass 9.1
27-21-01-20
EClass 10.0
27-21-01-20
UNSPSC
30-21-18-01

Output

Number of outputs
1
Output voltage, note
0...10 V
Output current
0(4)...20 mA
Load impedance voltage
≥ 1 kΩ
Load impedance current
≤ 600 Ω
Offset voltage
max. 0.02 V
Offset current
max. 40 µA
Status indicator
Green LED

Product Information

Product information
This product will soon be replaced by a new product.Please do not use with new systems. Please contact our technical support.

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

Clearance & creepage distances
Supply/output: 3 mm; Input/Output, Supply/output: 5.5 mm
EMC standards
EN 61000-2-6, EN 61000-6, EN 61326
Galvanic isolation
3-way isolator
Impulse withstand voltage
Supply⁄output: 4 kV; input/output, input/output: 6 kV
Insulation voltage
4 kVeff / 5 s
Insulation voltage input or output/supply
Input / power: 4 kVeff/ 5 s; output / power supply: 2 kVeff / 5 s
Pollution severity
2
Rated voltage
supply/output: 300 V; input/output, supply/output: 600 V
Surge voltage category
III

Temperatures

Operating temperature, max.
50 °C
Operating temperature, min.
0 °C
Storage temperature, max.
70 °C
Storage temperature, min.
-20 °C
Operating temperature
0 °C...50 °C
Storage temperature
-20 °C...70 °C

Ratings Iecex/Atex/Cul

Certificate no. (cULus)
E141197