ABB

B7-40-00-F-84

B7-40-00-F-84 Mini Contactor 110 ... 127 V AC - 4 NO - 0 NC - Flat-Pin Connections
B7-40-00-F-84
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Additional Information

Part Number
B7-40-00-F-84
UNSPSC
39121529
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Power contactor, AC switching
Class Code : EC000066
Version : 7

Dimensions

Product Net Width
52.5 mm
Product Net Height
57.5 mm
Product Net Depth / Length
46.7 mm
Product Net Weight
0.17 kg

Technical

Number of Poles
4
Mini Contactor Type
Mini Contactor
Rated Operational Voltage
Main Circuit 690 V ACMain Circuit 220 V DC
Rated Frequency (f)
Control Circuit 400 HzControl Circuit 50 HzControl Circuit 60 HzMain Circuit 60 HzMain Circuit 50 HzMain Circuit DC
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 6 kV
Rated Insulation Voltage (Ui)
690 Vacc. to UL/CSA 600 V
Number of Main Contacts NC
0
Number of Main Contacts NO
4
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 20 A(220 / 240 V) 55 °C 16 A(380 / 440 V) 40 °C 20 A(380 / 440 V) 55 °C 16 A(690 V) 40 °C 6 A(690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 3 kW(400 V) Three Phase 5.5 kW(500 V) Three Phase 5.5 kW(690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Number of Auxiliary Contacts NC
0
Number of Auxiliary Contacts NO
0
Conventional Free-air Thermal Current (Ith)
Main Circuit 20 A
Rated Control Circuit Voltage (Uc)
110 ... 127 V AC
Coil Operating Limits
(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Degree of Protection
Control Circuit Terminals IP20Main Circuit Terminals IP20
Mechanical Durability
10000000 cycle
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour(AC-3) 600 cycles per hour(DC-1) 600 cycles per hour(DC-3) 600 cycles per hour
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss
at Rated Operating Conditions per Pole 2 Wat Rated Operating Conditions AC-1 per Pole 1.4 W
Standards
IEC/EN 60947-1IEC/EN 60947-4-1IEC/EN 60947-5-1UL 60947-1UL 60947-4-1

Classifications

Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
EClass
V11.0 : 27371003
IDEA Granular Category Code (IGCC)
4761 >> Magnet contactor, AC-switching

Environmental

Ambient Air Temperature
Operation -25 ... +55 °CStorage -40 ... +80 °C
Maximum Operating Altitude Permissible
2000 m
Resistance to Shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to Vibrations acc. to IEC 60068-2-6
5g / 5 ... 150 Hz
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Technical UL/CSA

Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
Full Load Amps Motor Use
(115 V AC) Single Phase 13.8 A(200 V AC) Three Phase 7.8 A(220 ... 240 V AC) Three Phase 9.6 A(230 V AC) Single Phase 10 A(440 ... 480 V AC) Three Phase 7.6 A(550 ... 600 V AC) Three Phase 6.1 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.75 Hp(200 V AC) Three Phase 2 Hp(220 ... 240 V AC) Three Phase 3 Hp(230 V AC) Single Phase 1.5 Hp(440 ... 480 V AC) Three Phase 5 Hp(550 ... 600 V AC) Three Phase 5 Hp
General Use Rating UL/CSA
(600 V AC) 16 A

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85365080