ABB S804C-C125

S804C-C125 High Performance MCB

Image of the product S804C-C125
The S804C-C125 is a 4-pole High Performance Circuit breaker with C-characteristic, with cage terminal and a rated current of 125 A. It is a current limiting device with a maximum breaking capacity of 25kA at 240/415V. It can be used for voltages up to 254/440V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S804C-C125 complies with IEC/EN 60898-1 and IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S804C-C125 more comfortable. Due to the fast arc extinction of S804C-C125 your application will be secured.

Additional information

Part Number S804C-C125
UPC 54136567108440
ETIM Group code: EG000020
Group description: Circuit breakers and fuses
Class code: EC000042
Class description: Miniature circuit breaker (MCB)
Version: 7

Dimensions

Product Net Width 106 mm
Product Net Depth / Length 82.5 mm
Product Net Height 95 mm
Product Net Weight 980 g

Technical

Standards IEC/EN 60947-2IEC/EN 60898-1
Number of Poles 4
Number of Protected Poles 4
Tripping Characteristic C
Rated Current (In) 125 A
Rated Operational Voltage 254/440 V AC500 V DC
Power Loss at Rated Operating Conditions per Pole 9.4 W
Rated Insulation Voltage (Ui) 500 V AC
Operational Voltage Maximum 230/400 V ACMinimum 12 V AC
Rated Frequency (f) 50...60 Hz
Rated Short-Circuit Capacity (Icn) (400 V) 15 kA(230 V) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu) (240 / 415 V AC) 25 kA(254 / 440 V AC) 15 kA(500 V DC) 10 kA
Rated Service Short-Circuit Breaking Capacity (Ics) (240 / 415 V AC) 18 kA(254 / 440 V AC) 10 kA(500 V DC) 10 kA
Energy Limiting Class 3
Overvoltage Category IV
Pollution Degree 3
Rated Impulse Withstand Voltage (Uimp) 8 kV
Housing Material Insulation group I, RAL 7035
Actuator Marking I / O
Contact Position Indication ON / OFF / TRIP
Degree of Protection IP20
Remarks Connection from top and bottomConnecting with CU onlyIP40 in enclosure with coverCage terminal with captive screw
Electrical Endurance 4000 cycle
Mechanical Endurance (Nendu) 6000 cycle
Terminal Type Screw Terminals
Connecting Capacity Rigid 0 ... 50 mm²Flexible 0 ... 70 mm²
Tightening Torque 3.5 N·m31 in·lb
Recommended Screw Driver Pozidriv 2
Mounting on DIN Rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Position Any
Built-In Depth (t2) 82.5 mm

Container Information

Package Level 1 Units 1 piece
Package Level 1 Width 105 mm
Package Level 1 Depth / Length 111 mm
Package Level 1 Height 99 mm
Package Level 1 Gross Weight 1010 g
Package Level 1 EAN 5413656710844

Classifications

Object Classification Code F
ETIM 6 EC000042 - Miniature circuit breaker (MCB)
ETIM 7 EC000042 - Miniature circuit breaker (MCB)

Environmental

Ambient Air Temperature Operation -25...60 °C
Reference Ambient Air Temperature acc. to IEC60947-2 30 °Cacc. to EN60898-1 30 °C
Resistance to Shock acc. to IEC 60068-2-27 5 g30 ms
Resistance to Vibrations acc. to IEC 60068-2-6 2 - 13.2 Hz / 1mm13.2 - 100Hz / 0.7gwith load 100% x Ie
Environmental Conditions Damp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycleDamp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96%Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100%Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °CDry Heat Test B acc. to IEC 60068-2-2 2 hour @ 70 °C
RoHS Status Following EU Directive 2011/65/EU

Ordering

Minimum Order Quantity 1 piece
Customs Tariff Number 85362020