ABB
1SBL367201R1300
1 / 1
Beschreibung
The AF52-40-00-13 is a 4 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 22 kW / 400 V AC (AC-3) and switching power circuits up to 100 A (AC-1) or 80 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.- Country of Origin
- FR
- Part Number
- 1SBL367201R1300
- Tariff Code
- 85364900
- EAN
- 3471523133631
- UNSPSC
- 39121529
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : Power contactor, AC switching
- Class Code : EC000066
- Version : 7
€251.30
net1
Zahlungsmethoden:
- Bestes Angebot von:
- Vertrauenswürdiger Automa.Net Lieferant
- Verfügbarkeit:
- 3 Stk.Auf LagerAktualisiert am: 12-11-2024
- Geschätzte Lieferung:
- Auf Anfrage
- Zustand:
- Neu versiegelt ab Werk
Neu versiegelt ab Werk - Ein brandneuer, unbenutzter, ungeöffneter, unbeschädigter Artikel in seiner original vom Hersteller versiegelten Verpackung.
Sicherer Zahlungsprozess
Rückgabe- und Erstattungsrichtlinien
Versandrichtlinien
Garantiebedingungen
Dimensions
- Product Net Width
- 70 mm
- Product Net Depth / Length
- 113.5 mm
- Product Net Height
- 125.5 mm
- Product Net Weight
- 1.16 kg
Technical
- Number of Main Contacts NO
- 4
- Number of Main Contacts NC
- 0
- Number of Auxiliary Contacts NO
- 0
- Number of Auxiliary Contacts NC
- 0
- Standards
- IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
- Rated Operational Voltage
- Main Circuit 690 V
- Rated Frequency (f)
- Control Circuit 50 / 60 HzMain Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (Ith)
- acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
- Rated Operational Current AC-1 (Ie)
- (690 V) 40 °C 100 A(690 V) 60 °C 80 A(690 V) 70 °C 70 A
- Rated Operational Current AC-3 (Ie)
- (415 V) 60 °C 53 A(440 V) 60 °C 53 A(500 V) 60 °C 45 A(690 V) 60 °C 35 A(380 / 400 V) 60 °C 53 A(220 / 230 / 240 V) 60 °C 53 A
- Rated Operational Power AC-3 (Pe)
- (415 V) 30 kW(440 V) 30 kW(500 V) 30 kW(690 V) 30 kW(380 / 400 V) 22 kW(220 / 230 / 240 V) 15 kW
- Rated Short-time Withstand Current Low Voltage (Icw)
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
- Maximum Breaking Capacity
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
- Maximum Electrical Switching Frequency
- (AC-1) 600 cycles per hour
- Rated Insulation Voltage (Ui)
- acc. to IEC 60947-4-1 690 Vacc. to UL/CSA 600 V
- Rated Impulse Withstand Voltage (Uimp)
- 6 kV
- Maximum Mechanical Switching Frequency
- 3600 cycles per hour
- Rated Control Circuit Voltage (Uc)
- 50 Hz 100 ... 250 V60 Hz 100 ... 250 VDC Operation 100 ... 250 V
- Coil Consumption
- Average Holding Value 50 / 60 Hz 4 V·AAverage Holding Value 50 Hz 4 V·AAverage Holding Value 60 Hz 4 V·AAverage Holding Value DC 2 WAverage Holding Value, from Warm State 2 W
- Mounting on DIN Rail
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
- Mounting by Screws (not supplied)
- 2 x M4 or 2 x M6 screws placed diagonally
- Connecting Capacity Main Circuit
- Flexible with Ferrule 1/2x 4 ... 35 mm²Flexible with Insulated Ferrule 1/2x 4 ... 35 mm²Rigid Stranded 1/2x 6 ... 35 mm²
- Connecting Capacity Control Circuit
- Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid Solid 1/2x 1 ... 2.5 mm²Rigid Stranded 1/2x 1 ... 2.5 mm²
- Wire Stripping Length
- Control Circuit 10 mmMain Circuit 16 mm
- Degree of Protection
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
- Terminal Type
- Screw Terminals
Classifications
- Object Classification Code
- Q
- ETIM 4
- EC000066 - Magnet contactor, AC-switching
- ETIM 5
- EC000066 - Magnet contactor, AC-switching
- EClass
- V11.0 : 27371003
- IDEA Granular Category Code (IGCC)
- 4758 >> Iec Contactors
- E-Number (Finland)
- 3707262
- E-Number (Sweden)
- 3210311
Environmental
- Ambient Air Temperature
- Close to Contactor for Storage -60 ... +80 °CNear Contactor for Operation in Free Air -40 ... 70 °C
- Climatic Withstand
- Category B according to IEC 60947-1 Annex Q
- Maximum Operating Altitude Permissible
- Without Derating 3000 m
- Resistance to Vibrations acc. to IEC 60068-2-6
- 5 ... 300 Hz 3 g Closed position / 2 g Open position
- RoHS Status
- Following EU Directive 2011/65/EU
Technical UL/CSA
- Maximum Operating Voltage UL/CSA
- Main Circuit 600 V
- General Use Rating UL/CSA
- (600 V AC) 80 A
- Connecting Capacity Main Circuit UL/CSA
- Rigid Stranded 1/2x 10-2 AWG
- Connecting Capacity Control Circuit UL/CSA
- Rigid Solid 1/2x 18-14 AWGRigid Stranded 1/2x 18-14 AWG
- Tightening Torque UL/CSA
- Control Circuit 11 in·lbMain Circuit 35 in·lb
Ordering
- Minimum Order Quantity
- 1 piece
- Customs Tariff Number
- 85364900
Andere Kategorien
AktuatorenBlöckeKabel, Rohre & SchläucheKompressorenKontrolleKupplungen & FittingsZylinder & KolbenElektronikFilterHVACIndustrie-PCs & HMIsBeleuchtungLineartechnikMotorenStromversorgungLeistungsübertragungPumpen & VentileErneuerbare energieRobotikDichtungen, Ringe & VerbinderSensoren und MessgeräteWerkzeuge und ZubehörCNCSonstiges