- Standards
- CSA 22.2 No. 5IEC/EN 60947-2UL 489
- Tripping Characteristic
- K
- Rated Operational Voltage
- acc. to IEC 60947-2 400 V AC
- Operational Voltage
- Minimum 12 V AC
- Rated Insulation Voltage (Ui)
- acc. to IEC/EN 60664-1 440 V
- Rated Impulse Withstand Voltage (Uimp)
- 4 kVat 2000 m 5 kVat Sea Level 6.2 kV
- Dielectric Test Voltage
- 50/60 Hz, 1 min: 2 kV
- Rated Current (In)
- 3 A
- Rated Short-Circuit Capacity
- (AC) 10 kA(DC) 10 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu)
- (400 V AC) 25 kA
- Rated Service Short-Circuit Breaking Capacity (Ics)
- (400 V AC) 12.5 kA
- Rated Frequency (f)
- 50 / 60 Hz
- Power Loss
- 3.8 Wat Rated Operating Conditions per Pole 1.9 W
- Power Supply Connection
- Arbitrary
- Contact Position Indication
- Red ON / Green OFF
- Electrical Endurance
- 20000 AC cycle
- Mechanical Endurance
- 20000 cycle
- Number of Poles
- 2
- Number of Protected Poles
- 2
- Overvoltage Category
- III
- Tightening Torque
- 2.8 N·m
- Screw Terminal Type
- Failsafe Bi-directional Cylinder-lift Terminal
- Actuator Marking
- I / O
- Actuator Material
- Insulation Group II, Black, Sealable
- Housing Material
- Insulation Group I, RAL 7035
- Mounting on DIN Rail
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- Mounting Position
- any
- Recommended Screw Driver
- Pozidriv 2
- Accessories Available
- Yes
- Technical Information
- S202U-K3
- Connecting Capacity
- Busbar 10 / 10 mm²Flexible with Ferrule 0.75 ... 16 mm²Flexible 0.75 ... 16 mm²Rigid 0.75 ... 25 mm²Stranded 0.75 ... 25 mm²
- Installation Size
- acc. to DIN 43880 2
- Terminal Type
- Screw Terminals