Phoenix Contact
2701540
Distributed I/O device - AXL E ETH DI8 DO4 2A M12 6M - 2701540
- Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
- Wiederverkaufsrabatte bis zu 40%!
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Produktbedingungen:
Angebot mit Herstellervorlaufzeit
Lieferung:Auf Anfrage
Bester Preis:
Preisanfrage senden
Additional Information
- Part Number
- 2701540
- UPC
- 4046356763882
- Country of Origin
- DE
- ETIM
- Group Code : EG000024
- Group Description : PLC's
- Class Description : Fieldbus, decentr. periphery - digital I/O module
- Class Code : EC001599
- Version : 7
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 60 mm
- Height
- 185 mm
- Depth
- 38 mm
- Note on dimensions
- The height is 194.5 mm including the mounting plate. With fixing clips pulled out, the height is 212 mm. The depth is 38 mm including the mounting plate (30.5 mm without the mounting plate).
- Drill hole spacing
- 198.5 mm
System limits of the bus coupler
- Designation
- Modbus/TCP
- Equipment type
- Modbus slave (server)
- System-specific protocols
- Modbus protocols Modbus/TCP
- Protocols supported
- SNMP v1
- Protocols supported
- HTTP
- Protocols supported
- TFTP
- Protocols supported
- FTP
- Protocols supported
- BootP
- Protocols supported
- DHCP
- Specification
- Modbus application protocol V1.1b
Supply
- Designation
- Module electronics and sensors (US)
- Number of positions
- 4
- Supply voltage
- 24 V DC
- Current consumption
- typ. 140 mA ±15 % (at 24 V DC)
- Designation
- Actuators (UA)
- Connection method
- M12 connector (T-coded)
- Supply voltage range
- 18 V DC - 31.2 V DC (including all tolerances, including ripple)
- Current consumption
- typ. 30 mA ±15 % (at 24 V DC)
Digital inputs
- Input name
- Digital inputs
- Description of the input
- EN 61131-2 types 1 and 3
- Connection method
- M12 connector, double occupancy
- Connection technology
- 4-wire
- Number of inputs
- 8
- Protective circuit
- Overload protection, short-circuit protection of sensor supply
- Nominal input voltage UIN
- 24 V DC
- Nominal input current at UIN
- typ. 3 mA
- Input filter time
- < 1000 µs
- Cable length
- max. 30 m (To the sensor)
- Input voltage range "0" signal
- 0 V - 5 V DC
- Input voltage range "1" signal
- 11 V DC - 30 V DC
Ambient conditions
- Ambient temperature (operation)
- -25 °C - 60 °C
- Ambient temperature (storage/transport)
- -25 °C - 85 °C
- Permissible humidity (operation)
- 5 % - 95 %
- Permissible humidity (storage/transport)
- 5 % - 95 %
- Air pressure (operation)
- 70 kPa - 106 kPa (up to 3000 m above sea level)
- Air pressure (storage/transport)
- 70 kPa - 106 kPa (up to 3000 m above sea level)
- Degree of protection
- IP65/IP67
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 25;
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Electrical isolation
- Test section
- 24 V supply (communications power and sensor supply, digital inputs)/bus connection (Ethernet 1) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (communications power and sensor supply, digital inputs)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (communications power and sensor supply, digital inputs)/FE 500 V AC 50 Hz 1 min.
- Test section
- Bus connection (Ethernet 1)/FE 500 V AC 50 Hz 1 min.
- Test section
- Bus connection (Ethernet 2)/FE 500 V AC 50 Hz 1 min.
- Test section
- Bus connection (Ethernet 1)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (actuator supply, digital outputs)/24 V supply (communications power and sensor supply, digital inputs) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (actuator supply, digital outputs)/bus connection (Ethernet 1) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (actuator supply, digital outputs)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (actuator supply, digital outputs)/FE 500 V AC 50 Hz 1 min.
Digital outputs
- Output name
- Digital outputs
- Connection method
- M12 connector, (A-coded)
- Connection technology
- 3-wire
- Number of outputs
- 4
- Protective circuit
- Overload protection, short-circuit protection of outputs yes
- Output voltage
- 24 V DC
- Nominal output voltage
- 24 V DC (from voltage UA)
- Maximum output current per channel
- 2 A
- Nominal load, inductive
- 48 VA (1.2 H, 48 Ω, with nominal voltage)
- Nominal load, ohmic
- 48 W (48 Ω, with nominal voltage)
- Switching frequency
- max. 5500 per second (with at least 50 mA load current)
- Output voltage when switched off
- max. 1 V
- Output current when switched off
- max. 20 µA
- Behavior with overload
- Auto restart
- Reverse voltage resistance to short pulses
- Reverse voltage proof
Interfaces
- Designation
- Ethernet
- No. of channels
- 2
- Connection method
- M12 fast connection technology
- Note on the connection method
- D-coded
- Designation connection point
- Copper cable
- Transmission speed
- 10/100 Mbps (with auto negotiation)
- Number of positions
- 4
Standards and Regulations
- Mechanical tests
- Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
- Mechanical tests
- Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse
- Mechanical tests
- Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
- Protection class
- III (IEC 61140, EN 61140, VDE 0140-1)
CAD Models
traceparts
Herunterladen