- Ambient Air Temperature For Operation
- -25-60 °C
- Status Led
- 1 LED (Green) processor running (RUN) || 1 LED (Red) processor or system fault (ERR) || 1 LED (Red) I/O module fault (I/O) || 1 LED (Green) download in progress (DL) || 1 LED (Red) memory card or CPU flash fault (BACKUP) || 1 LED (green/red) ETH MS (Ethernet port configuration status) || 1 LED (green/red) Eth NS (Ethernet network status) || 1 LED (Green) peer processor running (REMOTE RUN) || 1 LED (Green) processor ID set to A (A) || 1 LED (Green) processor ID set to B (B) || 1 LED (Green) processor acting as Primary (PRIM) || 1 LED (Green) processor acting as Standby (STBY) || 1 LED (Red) I/O values overrided by user (FORCED IO) || 1 LED (Green) processor in safety mode (SRUN) || 1 LED (Green) processor in maintenance mode (SMOD) || 1 LED (Green) Hot standby link status (Hsby Diag)
- Standards
- IEC 61131-2 || IEC 61010-2-201 || UL 61010-2-201 || CSA C22.2 No 61010-2-201 || IACS E10 || EN/IEC 61000-6-5, interface type 1 and type 2 || EN/IEC 61850-3, location G || IEC 60079-0 || EN 50155 || EN 50121-3-2 || EN 50121-4 || EN 50121-5 || EN 45545-2 || IEC 60571 || IEC 62236-3-2 || IEC 62234-4 || IEC 62234-5
- Product Certifications
- CE || UL || CSA || RCM || EAC || Merchant Navy || ATEX zone 2/22 || IECEx zone 2/22 || TÜV
- Supply
- internal power supply via rack
- Shock Resistance
- 15 gn
- Environmental Characteristic
- hazardous location class I division 2 || gas resistant class Gx ISA S71.04 || gas resistant class 3C4 IEC 60721-3-3 || dust resistant class 3S4 IEC 60721-3-3 || sand resistant class 3S4 IEC 60721-3-3 || salt resistant level 2 IEC 68252 || mold growth resistant class 3B2 IEC 60721-3-3 || fungal spore resistant class 3B2 IEC 60721-3-3
- Vibration Resistance
- 3 gn
- Net Weight
- 0.849 kg
- Directives
- 2014/30/EU - electromagnetic compatibility || 2006/42/EC - machinery || 2014/34/EU - ATEX directive
- Ambient Air Temperature For Storage
- -40-85 °C
- Relative Humidity
- 5-95 % 55-55 °C without condensation
- Operating Altitude
- 0...6561.68 ft (0...2000 m) || 2000...5000 m with derating factor
- Protective Treatment
- conformal coating
- Ip Degree Of Protection
- IP20
- Safety Level
- SIL 3 IEC 61508 || SIL 3 IEC 61511 || SILCL 3 IEC 62061 || SILCL 3 ISO 13849-1 category 4 || SIL 4 EN 50126 || SIL 4 EN 50128 || SIL 4 EN 50129