Schneider Electric
GV4AS057
1 / 1
Beschreibung
Aktiv Reif
TeSys GV electrical trip unit, MX shunt trip, 48V AC 50Hz/60Hz or 48V DC, for motor circuit breakers GV4. It trips the circuit breaker when the control voltage is applied in limits 0.7-1.1 Uc with an impulse duration greater than 20ms or a maintained signal. To be plugged inside the circuit breaker, connection by spring terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).- Country of Origin
- FR
- Part Number
- GV4AS057
- Tariff Code
- 85363010
- EAN
- 3606485444895
- UNSPSC
- 39121010
- Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
- Wiederverkaufsrabatte bis zu 40%!
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Specifications
- [Uc] Control Circuit Voltage
- 48 V AC 50/60 Hz || 48 V DC
- Range Compatibility
- TeSys (TeSys GV4) || TeSys (TeSys BV4)
- Product Or Component Type
- voltage release
- Range
- TeSys
- Voltage Release Type
- shunt trip release
- Device Application
- control
- Device Short Name
- MX
Complementary
- Maximum Inrush Power In W
- 4 W
- Maximum Inrush Power In Va
- 6 VA
- Connections - Terminals
- spring terminals 1 0.5-1.5 mm² flexible without cable end
- Wire Stripping Length
- 8 mm
- [Ui] Rated Insulation Voltage
- 48 V IEC 60947-1
- Impulse Duration
- >= 20 ms
- Mounting Mode
- internal mounting
- Maximum Hold-In Power Consumption In W
- 1 W
- Mechanical Durability
- 20000 cycles
- Maximum Hold-In Power Consumption In Va
- 10 VA
- Threshold Tripping Voltage
- 0.7...1.1 Un failsafe opening || < 0.7 Un possible opening
- Operating Time
- < 50 ms
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Eu Rohs Directive
- Compliant
Environment
- Quantity Per Set
- set of 1
CAD Models
traceparts
Herunterladen